FC Flow Computer
54
6.8
FLOW INPUT
FLOW INPUT
FLOWMETER TYPE
Select the flowmeter type. The flow equation (see SYSTEM
PARAMETERS) and the flowmeter selected here determine the
basic operation of the flow computer.
Selection:
LINEAR
Volumetric flowmeter with linear pulse or analog
output.
SQR LAW
Differential pressure transmitter without square root
extraction, with analog output.
SQR LAW-LIN.
Differential pressure transmitter with square root
extraction and analog output.
LINEAR 16 PT*
Volumetric flowmeter with nonlinear pulse or analog
output; with 16 point linearization table.
SQR LAW 16 PT*
Differential pressure
transmitter without square root extraction, with analog
output and 16 point linearization table.
SQR LAW-LIN. 16 PT*
Differential pressure
transmitter with square root extraction, analog output
and 16 point linearization table.
LINEAR UVC
Volumetric Turbine flowmeter with UVC calibration
curve documentation and pulse output.
LINEAR MANIFOLD
Linear manifold consists of 2 linear flowmeters used in
conjunction with an external bypass/diverter value. It
may be used with turbine, PD, Mag, Vortex flowmeters
equipped with analog outputs to extend the allowable
turndown range.
GILFLO
Gilflo flowmeters are special purpose differential
pressure type flowmeters with an analog output where
the differential pressure is linear with flow.
GILFLO 16PT
Gilflo 16 PT flowmeters are special purpose differential
pressure type flowmeters with an analog output
where the differential pressure is approximately linear
with flow, but can be further enhanced by a 16 point
linearization table.
BYPASS
BYPASS is a selection for use with Bypass(Shuntflow)
flowmeters equipped with a pulse output.
ILVA 16PT
ILVA 16 PT flowmeters are special purpose differential
pressure type flowmeters with an analog output
where the differential pressure is approximately linear
with flow, but can be further enhanced by a 16 point
linearization table.
MASS FLOW METER
Flowmeter type such as Coriolis, or Thermal
Flowmeter whose output is directly proportional to
mass flow. Multivariable transmitters whose output is
proportional to a computed mass flow rate can also
use this meter type selection.
* A linearization table must be entered by user.
(see "LINEARIZATION" submenu).