The "display damping" constant is used to stabilize fluctuating
displays. The higher the constant, the less fluctuation will be
displayed.
Note: Relay response time is affected by the value entered for
display damping. The larger the display damping value,
the slower the relay response time will be. This is intended
to prevent false triggering of the relays. Enter a display
damping factor of zero (0) for fastest response time.
Note:
• Factory setting: 1
Input:
2 digits max; 0...99
Display:
CONSTANT? 1
DISPLAY DAMPING
Enter the number of decimal places for numerical values.
Note:
• The number of decimal places applies to all displayed
variables and totalizers.
• The number of decimal places is automatically reduced if
there is insufficient space available on the display for large
numbers.
• The number of decimal places set here does not affect the
functions set in the programming setup.
Selection:
0, 1, 2, 3 or 4 (decimal places)
Display:
3
MAX. DEC. POINT
The language can be selected in which all text, parameters and
operating messages are to be displayed.
Note:
• This function is supported by a special capability in the
setup diskette.
Selection:
ENGLISH, OTHER
Display:
ENGLISH
LANGUAGE
6.5
DISPLAY
(Continued)
DISPLAY
DISPLAY
DAMPING
MAX. DEC. POINT
LANGUAGE