SET PUlSE On TiME
The next programming parameter is Set Pulse On Time. The following message will display:
When it is required to Set Pulse On Time, enable the ENT key on this display. An enable to the increment key to Set
Pulse On Time will continue with the next programming parameter.
An enable to the ENT key will display the following message:
A Pulse On Time of 1 mSec to 99 mSec can be set in this subroutine.
SET alaRMS
The next programming parameter is Set Alarms. An enable to the ENT key will continue to this subroutine, while an
enable to the increment key will jump to the next programming parameter. High and low flow alarms can be set in
this programming menu.
A HI Flow Alarm can be set up to 110% of the maximum flow rate for a given NB size instrument.
A LO Flow Alarm can be programmed throughout the range provided. A HI Flow Alarm value should be greater than
the LO Flow Alarm value and the LO Flow Alarm value should be greater than the Creep Suppression Level.
An enable to the ENT key will enter into the programming menu. A HI Flow Alarm and LO Flow Alarm can be set in
the sequence in this parameter programming.
If Unit for Program is CuM/hr, the following message will display:
If Unit for Program is GPM, the following message will display:
An enable to the increment key will increment the digits by one, using the cursor. An enable to the ENT key will
accept the data and position the cursor to the next digit.
When the entry for the HI Alarm is complete, an enable to the ENT key will accept the data and will jump to the next
loop. An enable to the increment key will display the previous value of the LO Alarm.
If Unit for Program is CuM/hr, the following message will display:
Set
Pulse On Time?
Pulse On Time
20 mSec
Set alarms?
Enter hi alarm
70.00 CuM/hr
Enter hi alarm
308.0 gPM
Enter lO alarm
10.00 CuM/hr
Summary of Contents for 6600 Series
Page 13: ...NIAGARA Installation Operation Maintenance Manual M600 Rev E 10 ...
Page 14: ...11 Installation Operation Maintenance Manual M600 NIAGARA ...
Page 15: ...NIAGARA Installation Operation Maintenance Manual M600 Rev E 12 ...
Page 29: ...NIAGARA Installation Operation Maintenance Manual M600 Rev E 26 ...
Page 30: ...27 Installation Operation Maintenance Manual M600 NIAGARA ...