18
Wizard
Once you have selected to start the Wizard you will go through the following 12 windows
1)
2)
2)
2)
3)
4)
5)
5)
1)
Smart Config and Manual Config option
2)
Date and Time will be important for applications where the logging of events, alarms and faults is critical
3)
If SMART Config was selected these fields will be auto filled, it is important to have both Source 1 & 2 available during the SMART Config
4)
For use with BTS and ACBs the Switch Technology should be set to Circuit Breaker
5)
Modbus RTU communications as standard, if not using communications proceed with the OK button
If the ATyS is still not recognising the sources please check the source OP range settings match the application
requirements.
Under
Main Menu
–
Parameters
–
Network
Windage generators tend to run at a higher frequency when unloaded.
As a result the
S2 OF Fail %
(Threshold) and
S2 OF RESTORE %
(Hysteresis) settings may need to be increased to
allow for higher unloaded running frequency.
The frequency of the generator output should normalise once loaded.