17
Configuration
When configuring an ATyS C55/65 it is recommended to have both Source 1 and Source 2 available to ensure
settings match the required application.
NHP CIP Factory Settings
Language
English
Poles & Wires
3P+N
Nominal Voltage
415 V
Nominal Frequency
50 Hz
Phase Rotation
A
–
B
–
C
Application Type
MAIN
–
GEN
Source Priority
Source 1
Switch Technology
Circuit Breaker
(Custom)
Tripping Action
Total Inhibition
Date Format
DD/MM/YY
Date and Time
AEDT
Modbus Settings
Baud: 38400
Stop: 1 BIT
Parity: None
Address: 006
When purchasing a C55 or C65 outside of the
ATYSCxxCIPxxxx offerings you will be promoted with the
SMART Wizard configuration on first power up. As the
ATYSCxxCIPxxxx is tested in house at NHP manufacturing
prior to despatch this Wizard would have been preformed
and set to:
Navigate to the Wizard
Press the Back/Menu button
1.
2.
3.
4.
5.
6.
Or
Navigate to Parameters Menu
Press OK button to enter Parameters
Or
Navigate to Wizard Menu (
Last option
)
Enter the 1000 using the arrows and press OK button to confirm
Press OK button to enter Wizard
Time settings do not change with daylight savings and will need to
be kept up-to-date by the end user
NHP Custom Switch Technology Settings
Input 1
BREAKER 1 CLOSED (N/O)
Input 2
BREAKER 2 CLOSED (N/O)
Input 3
BREAKER 1 TRIPPED (N/O)
Input 4
BREAKER 2 TRIPPED (N/O)
If you would like another configuration follow the
below to get to the SMART Wizard.
Images are taken from Socomec C55/65 Manual for interface reference and don’t reflect the NHP factory settings
Input 3 and 4 must to be set in I/O settings and can’t be set via Wizard or Switch Technology Settings