PLATINUM Series Controllers User’s Guide
52
Reference Section: Programming Mode (PRoG)
7.4.1.8
Set Output to Soak Event Mode (PRoG > oUt1
–
oUt6 > ModE > SE.oN)
Activate Output to Soak Event Mode (SE.oN) during Soak segments in Ramp and
Soak programs when the Soak Event flag is set for that Soak segment. This can be
used to turn on auxiliary devices such as fans or stirrers.
7.4.2
Output Cycle Pulse Width (PRoG > oUt1
–
oUt6 > CyCL)
Select the Output Cycle Pulse Width (CyCL) parameter. This parameter is used to set the
control signal pulse width in seconds for DC pulse, mechanical relay, and solid state relay
(SSR) outputs.
Set a value.
Note:
For DC pulse and SSR outputs, choose a value between 0.1 and 199.0. (The default is
0.1s.) For mechanical relays, choose a value between 1.0 and 199.0. (The default is 5.0s.)
Confirm the value.
7.4.3
Analog Output Range (PRoG > oUt1
–
oUt6 > RNGE)
Select the Output Range (RNGE) parameter. This menu choice is only available for analog
outputs. The RNGE parameter is used for both Control and Retransmission Modes and
generally must be matched to the input range for whatever device the analog output is
driving.
Navigate to the desired setting. Settings include the following:
0–10 – 0 to 10 Volts (factory default)
0–5 – 0 to 5 Volts
0–20 – 0 to 20 mA
4–20 – 4 to 20 mA
0–24 – 0 to 24 mA
Select the desired range setting.