PLATINUM Series Controllers User’s Guide
51
Reference Section: Programming Mode (PRoG)
For ACtN, select the correct setting. Settings include the following:
RVRS – Off when Process Value is > Setpoint, and on when Process Value
is < Setpoint (e.g., heating); deadband is applied below Setpoint (factory
default)
dRCt – Off when Process Value is < Setpoint, and on when Process Value
is > Setpoint (e.g., cooling); deadband is applied above Setpoint
For dEAd, set the desired value. (The default is 5.0.)
Select the indicated ACtN setting, or confirm the dEAd value.
7.4.1.4
Output as Alarm 1 (PRoG > oUt1
–
oUt6 > ModE >
ALM.1)
Select this Output to be an Alarm using the Alarm 1 (ALM.1) configuration.
7.4.1.5
Output as Alarm 2 (PRoG > oUt1
–
oUt6 > ModE >
ALM.2)
Select this Output to be an Alarm using the Alarm 2 (ALM.2) configuration.
7.4.1.6
Retransmission (PRoG > oUt1
–
oUt6 > ModE >
RtRN)
Select Retransmission (RtRN) as the Operating Mode for the output. This option is
only available for analog outputs. Scaling is performed using absolute values
—
not
calculated counts. The retransmission signal type (voltage or current and range) is
set for this output using the
7.4.3 Analog Output Range (PRoG > oUt1–oUt6 > RNGE)
parameter. The retransmission signal is then scaled using the following 4
parameters. The unit will display the first scaling parameter, Rd1, after RtRN is
selected.
Navigate to the desired setting. Settings include the following:
Rd1 – Process reading 1; the process reading that corresponds to the
output signal oUt1
oUt1 – The output signal that corresponds to the process value Rd1
Rd2 – Process reading 2; the process reading that corresponds to the
output signal oUt2
oUt2 – The output signal that corresponds to the process value Rd2
Select the indicated setting.
Set the desired value.
Confirm the value.
7.4.1.7
Set Output to Ramp Event Mode (PRoG > oUt1
–
oUt6 > ModE > RE.oN)
Activate Output to Ramp Event Mode (RE.oN) during Ramp segments in Ramp and
Soak programs when the Ramp Event flag is set for that Ramp segment. This can be
used to turn on auxiliary devices such as fans or stirrers, secondary heaters, etc.