NewMar SPS 12-20 Installation & Operation Manual Download Page 12

P.O. Box 1306

 Newport Beach

   California 92663

   

  

Phone: 714-751-0488  

     Fax: 714-957-1621

     E-Mail: [email protected]

4.4 

Adjust Boost to Float Current Threshold

Connect a variable load (set to minimum load) to the battery connections of the SPS. Disconnect the Temperature 

Compensation Probe. Connect an accurate current meter in series with the load. Turn on AC to the unit, wait 10 

seconds and then adjust the load up slowly until the unit goes into Boost Charge mode (as indicated on the LEDs). 

Slowly decrease the load until the rectifier switches to Float Charge mode. 

Note that there is a 10 second delay when switching from Boost Charge mode to Float Charge mode, but no delay 

when switching from Float to Boost.

Adjust the Boost to Float Current trimpot to set the required current value (0.1A to 40% of full load).

4.5 

Adjust Current Limit

Connect a variable load (set to minimum load) to the load connections of the SPS. Disconnect the Temperature 

Compensation Probe. Connect an accurate current meter in series with the load. Turn on AC to the rectifier and 

adjust the load until the rectifier goes into current limit (as indicated on the LEDs).

Adjust the Current Limit trimpot slowly to set the required current limit. Do not exceed 100% of the rated current. 

Note that the current output requires time to settle when you adjust the trimpot.

4.6 

Adjust Over-Voltage Shutdown

This adjustment requires a variable voltage power supply (that has a maximum voltage exceeding the over-

voltage value to be set).

Connect the variable voltage power supply across the load connections of the SPS (ensure that +v output of the 

variable supply is connected to the +v load connection). Disconnect the Temperature Compensation Probe. 

Connect an accurate voltmeter across the output. Turn the mains on to the rectifier and adjust the variable 

voltage power supply up until the unit goes into over-voltage shutdown (as indicated on the LEDs).

Adjust the Over-Voltage Shutdown trimpot to set the required voltage limit. Note that the SPS will cycle on and off 

– this is normal.

4.7 

Adjust Low Voltage Disconnect and Hysterisis

This adjustment requires a variable voltage power supply (that has a maximum voltage exceeding the voltage 

value to be set). 

Connect the variable voltage power supply across the battery connections of the rectifier (ensure that +v output 

of the variable supply is connected to the +v battery connection). Connect an accurate voltmeter across the load 

connections of the rectifiers.

Leave the rectifier disconnected from the AC. Switch on the variable power supply and adjust the voltage up until 

there is voltage on the load connections. Adjust the variable voltage down slowly until the load voltage drops 

suddenly, indicating the load has been disconnected.

First - Adjust the LVD Voltage trimpot to set the required ‘on’ voltage limit.

Second - Adjust the LVD Hysterisis trimpot to set the required ‘off’ voltage limit.

4.8 

Adjust Temperature Compensation Slope

The rectifier assumes that the battery temperature is 25°C when the Temperature Compensation Probe is not 

connected. Disconnect the Temperature Compensation Probe, and adjust the boost and float charge voltages to 

that required for 25°C. Reconnect the Temperature Compensation Probe and cool the metal lug to 0°C (using a 

container containing ice and water - 

do not

 immerse the probe in the water as it is not waterproof). 

Adjust the Temperature Compensation Slope to set the required charging voltage at this temperature as 

determined by the manufacturer’s specification.

12

Summary of Contents for SPS 12-20

Page 1: ...2 Troubleshooting 10 1 9 Input Over Voltage Shut Down 4 3 3 Fuses 10 1 10 Input Inrush Current Limiter 4 4 Adjustments 10 1 11 Over Temperature Shutdown 4 4 1 Standard Settings 11 1 12 Reverse Polari...

Page 2: ...e the present state of the rectifier and diagnose faults AC On This LED glows green to indicate that AC power is connected to the unit and that the primary stages of the rectifier are operating Shutdo...

Page 3: ...ches the battery ve supply the v is common with the battery Do not connect the Battery and Load v together The LVD voltage and the LVD Hysterisis voltage are preset in the factory but may be adjusted...

Page 4: ...if they fail 1 13 Parallel Rectifier Operation The SPS may be connected in parallel to source more current or to provide a degree of redundancy The rectifiers should have the load share signal connect...

Page 5: ...ethal even after the input supply has been removed The rectifier contains components at High Temperatures that may burn if touched 2 2 Positioning of SPS A great deal of care should be taken with posi...

Page 6: ...t outlet be used so the rectifier will not be accidentally unplugged from the supply When hard wiring AC input the IEC AC cord provided should be wired as follows BLK WHT GRN 120 VAC L N Safety Ground...

Page 7: ...w an internal protection fuse requiring the SPS to be returned for servicing Do not connect the Temperature Compensation Probe to the Site Power System until commissioning see Section 2 7 Start Up 2 5...

Page 8: ...fier Fail alarm Rectifier Off Normal and the Low Volts alarms will also activate Note that the AC Fail Relay has its own Common connector but all the other alarm outputs share a Common contact 2 6 2 R...

Page 9: ...y connections and then plug them into the SPS Re connect the mains and the Float Boost LED should glow first yellow then after about 10 seconds either green or yellow depending on the charge of the ba...

Page 10: ...e current drawn by the battery from the SPS is as expected Check that the battery takes the charge Connect the DC load to the SPS with AC off and disconnect the battery Turn AC on and check that the c...

Page 11: ...m back of unit with AC input socket on left 4 2 Adjust Float Voltage Connect a variable load set to minimum load to the battery connections of the rectifier Disconnect the Temperature Compensation Pro...

Page 12: ...ction Disconnect the Temperature Compensation Probe Connect an accurate voltmeter across the output Turn the mains on to the rectifier and adjust the variable voltage power supply up until the unit go...

Page 13: ...ature Compensation Probe Connect an accurate voltmeter across the output Turn AC and adjust the variable voltage power supply up until the alarm activates Adjust the Alarm Output High trimpot to adjus...

Page 14: ...P O Box 1306 Newport Beach California 92663 Phone 714 751 0488 Fax 714 957 1621 E Mail techservice newmarpower com 7 Dimensional Drawings 14...

Reviews: