To adjust the settings, appropriate test equipment is necessary (depending on the adjustment). A variable 

load, a variable DC power supply, and an accurate voltage and current meter are required. The SPS should be 

unscrewed from its mounting. The SPS must be disconnected from the battery and load. The adjustment trimpots 

are accessible on the rear side of the rectifier, with  the AC input oriented to the left, the trimpots read as follows. 

4.1 Standard Settings

Item

SPS 12-20

SPS 24-10

SPS 48-6

Boost Voltage

14.2V

28.8V

57V

Float Voltage

13.7V

27.4V

54V

Boost to Float Current

2A

1A

0.5A

Over Voltage Shutdown

16V

32V

60V

Temp Comp 25° C

13.7V

27.4V

54V

Temp Comp 5° 

14.06V

28.32V

55.9V

LVD On Voltage

12V

24V

48V

LVD Off Voltage

10V

20V

40V

Current Limit

20A

10A

6A

Trimpot View Orientation: From back of unit with AC input socket            on left.

4.2 

Adjust Float Voltage

Connect a variable load (set to minimum load) to the battery connections of the rectifier. Disconnect the 

Temperature Compensation Probe. Connect an accurate voltmeter across the load. Turn on AC to the unit. Wait 

approximately 10 seconds for it to switch back to Float Charge mode. Check that the LEDs indicate Float Charge 

mode.

Adjust the Float Voltage trimpot to set the required float voltage.

4.3 

Adjust Boost Voltage

Connect a variable load (set to minimum load) to the battery connections. Disconnect the Temperature 

Compensation Probe. Connect an accurate voltmeter across the load. Turn on AC to the unit and adjust the load 

until the unit goes into Boost Charge mode (as indicated on the LEDs). 

Note that there is a 10 second delay when switching from Boost Charge mode to Float Charge mode, but no delay 

when switching from Float to Boost.

Adjust the Boost Voltage trimpot to set the required boost voltage.

LVD 

Hystersis

LVD 

Voltage

Current 

Limit

Float 

Voltage

Boost 

Voltage

Temp Comp

Slope

Boost to Float

Current

Over-Voltage

Shutdown

11

Summary of Contents for SPS 12-20

Page 1: ...2 Troubleshooting 10 1 9 Input Over Voltage Shut Down 4 3 3 Fuses 10 1 10 Input Inrush Current Limiter 4 4 Adjustments 10 1 11 Over Temperature Shutdown 4 4 1 Standard Settings 11 1 12 Reverse Polari...

Page 2: ...e the present state of the rectifier and diagnose faults AC On This LED glows green to indicate that AC power is connected to the unit and that the primary stages of the rectifier are operating Shutdo...

Page 3: ...ches the battery ve supply the v is common with the battery Do not connect the Battery and Load v together The LVD voltage and the LVD Hysterisis voltage are preset in the factory but may be adjusted...

Page 4: ...if they fail 1 13 Parallel Rectifier Operation The SPS may be connected in parallel to source more current or to provide a degree of redundancy The rectifiers should have the load share signal connect...

Page 5: ...ethal even after the input supply has been removed The rectifier contains components at High Temperatures that may burn if touched 2 2 Positioning of SPS A great deal of care should be taken with posi...

Page 6: ...t outlet be used so the rectifier will not be accidentally unplugged from the supply When hard wiring AC input the IEC AC cord provided should be wired as follows BLK WHT GRN 120 VAC L N Safety Ground...

Page 7: ...w an internal protection fuse requiring the SPS to be returned for servicing Do not connect the Temperature Compensation Probe to the Site Power System until commissioning see Section 2 7 Start Up 2 5...

Page 8: ...fier Fail alarm Rectifier Off Normal and the Low Volts alarms will also activate Note that the AC Fail Relay has its own Common connector but all the other alarm outputs share a Common contact 2 6 2 R...

Page 9: ...y connections and then plug them into the SPS Re connect the mains and the Float Boost LED should glow first yellow then after about 10 seconds either green or yellow depending on the charge of the ba...

Page 10: ...e current drawn by the battery from the SPS is as expected Check that the battery takes the charge Connect the DC load to the SPS with AC off and disconnect the battery Turn AC on and check that the c...

Page 11: ...m back of unit with AC input socket on left 4 2 Adjust Float Voltage Connect a variable load set to minimum load to the battery connections of the rectifier Disconnect the Temperature Compensation Pro...

Page 12: ...ction Disconnect the Temperature Compensation Probe Connect an accurate voltmeter across the output Turn the mains on to the rectifier and adjust the variable voltage power supply up until the unit go...

Page 13: ...ature Compensation Probe Connect an accurate voltmeter across the output Turn AC and adjust the variable voltage power supply up until the alarm activates Adjust the Alarm Output High trimpot to adjus...

Page 14: ...P O Box 1306 Newport Beach California 92663 Phone 714 751 0488 Fax 714 957 1621 E Mail techservice newmarpower com 7 Dimensional Drawings 14...