I) OVERVIEW 

The Power Function Manager (model PFM-500) converts multiple DC power sources (or NEWMAR Power Modules) into a 

fully integrated and multi-functional power system. The unit provides control, monitoring, paralleling and protection of 

12V, 24V or 48V DC, positive, negative or floating ground power sources.
A heavy duty 

(500 amp)

 parallel bus bar, digital metering, individual power source and total system status lights, five 

load distribution breaker capacity, low voltage battery disconnect and summary alarm contacts are all combined into the 

compact, rackmount housing of the PFM, which serves as a master DC power management and distribution center.
The PFM may be used for integration, control, monitoring and protection of numerous different types of power sources, 

such as AC-DC rectifiers, regulated power supplies or DC-DC converters. In addition, any rack power product, including 

distribution panels, can be connected to the PFM's alarm system, provided they employ form C or Normally Open (NO) 

alarm contacts. For simplicity of explanation in this manual, reference is made to the NEWMAR Power Module as the 

power source(s).

Note: Installation of Oring diodes is required for paralleling of DC power sources. Oring diode output is standard on NEWMAR PM 
Series Power Modules.

II) INSTALLATION

A) Materials Provided

Prior to installation, please check to see that each of the following items have been included with the PFM. Check both the 

information packet and the cardboard insert which is labeled "ACCESSORIES INSIDE". For any missing items please contact 

the factory or warehouse.

B) PFM Mounting

The PFM is designed for mounting in a 19" or 23" relay rack and occupies two rack-units (2RU; 3.5"). A 19" set of mounting 

ears and six 6-32 x 3/8" pan head phillips screws for attaching the ears to the PFM chassis are provided. Optional 23" rack 

mounting ears are available - please contact Newmar for P/N: 699-3918-0, qty 2. Attachment holes in the chassis are 

provided to allow either flush or 6" off-set or center mounting - rear support is required if choosing flush mounting. 

C) Bus Bar Mounting

The PFM is shipped with a rackmount ground bus bar assembly kit (BBA-800). The bus bar is typically mounted on the rear 

of the rack and is designed for installation on 19" or 23" racks using the provided mounting brackets and isolated stand-

offs. Refer to the instruction sheet provided with the BBA for complete mounting instructions and specifications.

BBA and PFM Rack Location Note:

 When wiring multiple power sources for parallel n+1 redundant wiring, equal length 

positive and negative conductors are required for optimum load current sharing. Mounting the BBA at the opposite end 

of the rack as the PFM (i.e., BBA at top-of-rack; PFM at bottom, or vice versa) will help facilitate equal length conductor 

wiring.

D) Input Voltage Selection (Universal) and Wiring

The PFM has a universal input so no input selection switch is required. It will operate on 12, 24, or 48V DC with positive or 

negative ground.

1) Simplified Wiring Option: DC Quick Connect Wiring Kit

A DC wiring harness quick connect kit is available from NEWMAR which simplifies parallel wiring installation of 

multiple Power Modules with the Power Function Manager, and also facilitates “hot change-out” of modules for repair or 

replacement. 

Note: This option is available only for systems which incorporate 1,000 watt models of the NEWMAR PM Series Power 

Modules.

The kit consists of a power wiring harness with wires which are pre-cut to proper length and properly terminated with ring 

lugs. The harness is neatly tie-wrapped into proper position for a simple and professional installation.

(2)   ea. Mounting Ears for 19" rack mounting

(6)   ea. 6-32 X 3/8" Phillips Screws (for mounting ear)

(1)   ea. Circuit Breaker Finger Guard Cover 

(2)   ea. 6-32 x 1-3/8" Phillips Screw (Finger Guard Cover) 

(2)   ea. #6 23MM Spacer (Finger Guard Cover)

(1)   set Circuit Breaker Identification Labels

(1)   ea. Status Contact Wiring Harness with  

 

3 position connectors

(3)   ea. 3 Position Terminal Block Connector for Summary,  

 

Pre-LVD and LVD Alarm Contacts

(6)   ea. 1/4"-20 x 1" Hex Head Screws S.S. (Input/Output   

 

Busbar Wiring)

(11) ea. 1/4"-20 Hex Nut S.S. (Input/Output Busbar Wiring)

(11) ea. Flat Washers S.S. (Input/Output Busbar Wiring)

(11) ea. 1/4" Split Lock Washers S.S. (Input/Output Busbar  

 Wiring)

(5)   ea. 1/4"-20 x 3/4" Hex Head Screws S.S. (Hot  

 

Switch Outputs)

(1)  ea. BBA-800 Bus Bar Assembly Kit (see BBA instructions  

 

for parts diagram)

(1)   ea. Installation/Operation Manual

Summary of Contents for PFM-500

Page 1: ...ng E Output Wiring 5 1 Unswitched Output 2 Switched Output F Battery Wiring 6 G Status and Alarm Contact Wiring 7 H Chassis Grounding 8 I Circuit Breakers 8 1 Breaker Installation 2 Breaker Functions...

Page 2: ...TERY POSITIVE NEGATIVE OR FLOATING GROUND STATUS CONTACTS RETURN GND INPUT 1 INPUT 2 INPUT 3 LVD SUMMARY ALARM OUTPUT INPUT 4 INPUT 5 INPUT 6 NC NO C CONTACTS SHOWN IN FAILED POSITION 1 2 3 1 2 3 1 2...

Page 3: ...osing flush mounting C Bus Bar Mounting The PFM is shipped with a rackmount ground bus bar assembly kit BBA 800 The bus bar is typically mounted on the rear of the rack and is designed for installatio...

Page 4: ...Hot Wire to POSITIVE OUTPUT Terminal Positive Ground Systems Connect Ground Wire to POSITIVE OUTPUT Terminal and Hot Wire to NEGATIVE OUTPUT Terminal Power Plugs shown present only if using NEWMAR QC...

Page 5: ...for proper PFM input wire gauges 3 A return ground wire must also be run from the BBA bus bar or other grounding point to the terminal on the PFM labeled RETURN GND This is not a system ground rather...

Page 6: ...s requires installation of a model PBA plug in breaker available from NEWMAR at that position See section II I Fig 7 for installation details and breaker functions See section VII for available ampera...

Page 7: ...ness is designed for installations which employ NEWMAR Power Modules though it may be modified for use with other types of equipment as well provided they are equipped with Form C or Normally Open N O...

Page 8: ...nd a summary alarm from the DST is required this may be accomplished through parallel wiring of the status wires Please contact the factory for information on how to perform this modification When wir...

Page 9: ...reaker receptacle and pushing firmly into place The two top auxiliary contact terminals in the middle of the breaker should press against the mating clips The bottom auxiliary contact is unused in thi...

Page 10: ...e or the battery side by using the selector switch on front panel Powering the meter from the rectifier side default causes the PFM 500 to completely shutdown during a Low Battery Voltage Disconnect t...

Page 11: ...8 Fax 714 856 9679 E Mail techservice newmarpower com PoweringTheNetwork com C LCD Display 1 Digital Meter Programming Sequence Flow Chart Figure 8 Digital Meter Programming Sequence Flow Chart see pa...

Page 12: ...voltage disconnect Screen press programming button to enter set mode rotate knob to change push to confirm setting See page 13 for detailed directions 4B LVD voltage connect Screen press programming...

Page 13: ...ngs and is retained even after powering down the unit LVD threshold adjustment can be made while the system is operating 3 LVD Alarms Pre disconnect disconnect Two external alarms can be triggered by...

Page 14: ...Section III D for LVD adjustment procedure 4 PFM load circuit breaker tripped Breaker is in mid trip position Note Breaker will not activate the ALARM L E D if manually switched into the off position...

Page 15: ...power com Anytime We are happy to consult with you to resolve any problems or questions you may have If during consultation it appears the PFM must be returned to the factory for repair we will issue...

Page 16: ...low TEMPERATURE RATING 0 C to 60 C CASE SIZE H x W x D 3 5 x 19 or 23 x 20 5 LVD SPECIFICATIONS Factory set actuation voltages 12 Volt 24 Volt 48 Volt Disconnect 10 4V DC 21 0V DC 42 0V DC Connect 12...