background image

8

15272 Newsboy Circle
Huntington Beach
California 92649

                              

  

Phone:  714-751-0488  

                                     Fax: 714-856-9679

     E-Mail: [email protected]

PoweringTheNetwork.com

Status Contact Harness Connection

A typical system with three NEWMAR Power Modules is illustrated on the previous page. The provided status contact 

harness may also be used with non-NEWMAR equipment, however, it is likely that each connector on the harness 

which would normally plug into the power module will require removal and replacement with another suitable for that 

particular piece of equipment.
Careful attention to correct wire connections will be required when installing an alternate connector due to the uniform 

color of each wire group. Wiring from the alternate equipment contacts to the PFM contacts must be identical: (fail-to-fail, 

OK-to-OK) and Common-to-Common. “FAIL” and “OK” contact positions are illustrated on the rear of the unit beneath the 

Hot Output terminal. (Or see FIGURE 6, following.)

Alarm Wiring with NEWMAR DST-20A Distribution Panel

NEWMAR's DST-20A is provided with its own four-wire harness for alarm wiring. Plug one end of the harness into the keyed 

connector on the rear of the DST which is labeled BREAKER STATUS. Note: The harness is reversible, therefore it does not 

matter which end is plugged in. For PFM-500 use, cut off one Molex connector from the 

DST-20A harness and parallel the brown and blue wires. Parallel the orange and yellow wires. Select an un-used STATUS 

CONTACT Input and connect the parallel brown/blue wires to terminal #1 and the paralleled 

orange/yellow wires to terminal #3.
If all STATUS CONTACT positions are occupied (i.e., fi ve or six Power Modules are in the system), and a summary alarm 

from the DST is required, this may be accomplished through parallel wiring of the status wires. Please contact the factory 

for information on how to perform this modifi cation.
When wired to the PFM in this fashion any tripped breaker within the DST will result in illumination of the ALARM light on 

the front of PFM, as well as activation of the PFM summary alarm contacts.

Summary Alarm Wiring

The summary alarm contacts will be in the “FAIL” position under the identical conditions in which the “CHECK SYSTEM” 

indicator on the front panel is illuminated. (See Section III - B: Meter & Indicator for a complete description of failure 

conditions.)
This alarm may be wired with the relay “normally open” or “normally closed”, as required for the installation. The position 

of the contacts during DC output failure and normal operating condition is illustrated below:

FIGURE 6: DC “FAIL” and DC “OK” Summary Alarm Contact Positions (as viewed from rear of chassis)

 

 

Note: The three right-hand connector positions are unused in this installation

Relay contact rating for status and summary alarms is 5a @ 30V DC

H) Chassis Grounding

If grounding of the PFM chassis is required for the installation, use the provided 1/4" grounding stud on the rear panel 

identifi ed as “CHASSIS GND” for this purpose. 

Note: Do not confuse the chassis ground with the smaller return ground labeled 

“RETURN/GND”, also on the rear panel of the PFM.

I) Circuit Breakers
1) Circuit Breaker Installation

Circuit breakers must be installed to use any of the switched outputs. The PFM accepts only specially designed plug-in 

“mid-trip” circuit breakers with auxiliary contacts, which are available from NEWMAR. (The mid-trip function is explained 

later). Refer to the Specifi cations section for available breaker values and ordering info.
Refer to 

Figure 7

, on the next page and install the plug-in circuit breakers as follows:

Summary of Contents for PFM-500

Page 1: ...ng E Output Wiring 5 1 Unswitched Output 2 Switched Output F Battery Wiring 6 G Status and Alarm Contact Wiring 7 H Chassis Grounding 8 I Circuit Breakers 8 1 Breaker Installation 2 Breaker Functions...

Page 2: ...TERY POSITIVE NEGATIVE OR FLOATING GROUND STATUS CONTACTS RETURN GND INPUT 1 INPUT 2 INPUT 3 LVD SUMMARY ALARM OUTPUT INPUT 4 INPUT 5 INPUT 6 NC NO C CONTACTS SHOWN IN FAILED POSITION 1 2 3 1 2 3 1 2...

Page 3: ...osing flush mounting C Bus Bar Mounting The PFM is shipped with a rackmount ground bus bar assembly kit BBA 800 The bus bar is typically mounted on the rear of the rack and is designed for installatio...

Page 4: ...Hot Wire to POSITIVE OUTPUT Terminal Positive Ground Systems Connect Ground Wire to POSITIVE OUTPUT Terminal and Hot Wire to NEGATIVE OUTPUT Terminal Power Plugs shown present only if using NEWMAR QC...

Page 5: ...for proper PFM input wire gauges 3 A return ground wire must also be run from the BBA bus bar or other grounding point to the terminal on the PFM labeled RETURN GND This is not a system ground rather...

Page 6: ...s requires installation of a model PBA plug in breaker available from NEWMAR at that position See section II I Fig 7 for installation details and breaker functions See section VII for available ampera...

Page 7: ...ness is designed for installations which employ NEWMAR Power Modules though it may be modified for use with other types of equipment as well provided they are equipped with Form C or Normally Open N O...

Page 8: ...nd a summary alarm from the DST is required this may be accomplished through parallel wiring of the status wires Please contact the factory for information on how to perform this modification When wir...

Page 9: ...reaker receptacle and pushing firmly into place The two top auxiliary contact terminals in the middle of the breaker should press against the mating clips The bottom auxiliary contact is unused in thi...

Page 10: ...e or the battery side by using the selector switch on front panel Powering the meter from the rectifier side default causes the PFM 500 to completely shutdown during a Low Battery Voltage Disconnect t...

Page 11: ...8 Fax 714 856 9679 E Mail techservice newmarpower com PoweringTheNetwork com C LCD Display 1 Digital Meter Programming Sequence Flow Chart Figure 8 Digital Meter Programming Sequence Flow Chart see pa...

Page 12: ...voltage disconnect Screen press programming button to enter set mode rotate knob to change push to confirm setting See page 13 for detailed directions 4B LVD voltage connect Screen press programming...

Page 13: ...ngs and is retained even after powering down the unit LVD threshold adjustment can be made while the system is operating 3 LVD Alarms Pre disconnect disconnect Two external alarms can be triggered by...

Page 14: ...Section III D for LVD adjustment procedure 4 PFM load circuit breaker tripped Breaker is in mid trip position Note Breaker will not activate the ALARM L E D if manually switched into the off position...

Page 15: ...power com Anytime We are happy to consult with you to resolve any problems or questions you may have If during consultation it appears the PFM must be returned to the factory for repair we will issue...

Page 16: ...low TEMPERATURE RATING 0 C to 60 C CASE SIZE H x W x D 3 5 x 19 or 23 x 20 5 LVD SPECIFICATIONS Factory set actuation voltages 12 Volt 24 Volt 48 Volt Disconnect 10 4V DC 21 0V DC 42 0V DC Connect 12...

Reviews: