POSSIBLE CAUSE
CORRECTIVE ACTION
PROBLEM
D. LVBD will not connect battery to PFM
although battery is fully charged.
1. LVD out of adjustment.
1. See section III-D for LVD adjustment
procedure.
2. LVD selector is in “MANUAL
DISCONNECT” position.
2. Reposition switch to “AUTO”.
Factory Contact Information
If a problem with the PFM-500 persists after you have applied the above-outlined solutions, or if you have any
questions about the installation and proper operation of the unit, please contact NEWMAR's Technical Services
Manager:
Phone: 714-751-0488 — From the hours of 7:00 A.M. to 4:30 P.M. weekdays, P.S.T.
Fax: 714-856-9679 — Anytime
E-Mail: [email protected] — Anytime
We are happy to consult with you to resolve any problems or questions you may have. If, during consultation, it
appears the PFM must be returned to the factory for repair we will issue a Return Materials Authorization at that
time.
E) Meter Display Errors
LCD display gets out of sync with the
micro-controller and displays incorrect
information.
Power cycle the LCD. To power cycle
the meter without disconnecting the
load: first ensure
the rectifiers are on, disconnect
battery from PFM, then slide the
meter power to ‘Battery’ then back to
‘Rectifier’. This will briefly disconnect
power to the meter and allow a safe
power cycling and clear the display
error. Reconnect battery to PFM.
F) LVD Stability Issues After Settings
Change
LVD contactor cycles frequently after
making changes to the LVD
default settings
PFM-500 can be restored to factory
settings to aid in troubleshooting (see
section III page 12, item 4-4E and the
Digital Meter Programming Sequence
Fow Chart, page 11 for details).