ADM-M land call modul
Terminalassignmentandconfiguration
10
ADMmanual
4.2.4 Micromatch
ADM-M
Standard Programming
X3 Pin 1
X3 Pin 2/3
X3 Pin 4
landing call release
Call UP
+24V
X4 Pin 1
X4 Pin 2/3
X4 Pin 4
landing call release
Call DOWN
+24V
X5 Pin 2/3
X5 Pin 4
Out-of-order, special drive, occupied display
left, chime ,EAZ BIT5, chime left, special
drive left
+24V
X7 Pin 2/3
X7 Pin 4
direction UP
+24V
X8 Pin 2/3
X8 Pin 4
direction DOWN
+24V
X9 Pin 1
X9 Pin 2/3
X9 Pin 4
direction UP
+24V
direction DOWN
Terminals for which several functions are listed can be set with one of them at the factory. The „Direction“ func-
tion can be configured in the FST menu as a direction of travel output or a travel continuation output.
The terminals labelled with key switches 1 and 2 can be set at the factory with the functions fire recall, smoke
alarm, remote shutdown and priority landing.
Other I/O functions can be set using the software.
4.2.5 LED and micro fuse
colour
State
Description
yellow
briefly flashes after beeing switched on
ADM ready
flashing or permanently illuminated
hardware error
green
flashing
normal function
red
permanently illuminated
ADM damaged, replace it
The micro fuse with 250 mA is placed at the front of the module und protecs the circuit board. If the micro fuse is
damaged, the red LED between connector X1 and X2 will illuminate permanently.