ADM-M land call modul
Terminalassignmentandconfiguration
ADMmanual
9
4.2
Terminal assignment and configuration
4.2.1 Bus connection X1, X2
ADM-M X1 / X2
Cable colour
Designation
1
black
RS-485 LON bus A
2
white
RS-485 LON bus B
3
red
+24 V
4
violet
GND or 0V
4.2.2 Jumper
There are two contact areas on the ADM-M module instead of Jumper J1. If necessary, gently press these con-
tact area with a screwdriver.
4.2.3 Terminal strip
ADM-M X6
Standard Programming
X6.11
GND
X6.12
Key switch 1:
fire recall, fire recall selective, fire recall
reset, landing prio, landing prio selective,
landing prio super, remote shutdown,
remote shutdown selective, smoke alarm,
soft switch
X6.13
Key switch 2:
fire recall, fire recall selective, fire recall
reset, landing prio, landing prio selective,
landing prio super, remote shutdown,
remote shutdown selective, smoke alarm,
soft switch
X6.14
acoustic click
X6.15
+24V
X6.16
direction DOWN
X6.17
direction UP
X6.18
Key switch 3
X6.19
currently without function
X6.20
GND
X6.21
currently without function