Network Technologies Incorporated ENVIROMUX E-BCN-R Installation Manual Download Page 3

NTI ENVIROMUX SENSOR INSTALLATION 

 

2

INTRODUCTION  

 

 

 

 

 

 

 

 

 

 

Many different sensors can be connected to the ENVIROMUX Series Enterprise Environment Monitoring Systems.  Series models 
include E-16D/5D/2D,  E-MINI-LXO and E-MICRO-T(RHP).   A complete listing of available sensors and accessories can be found 
at  

http://www.networktechinc.com/environment-monitor-16d.html

 for the E-16D, 

http://www.networktechinc.com/environment-monitor-5d.html

  for the E-5D, 

http://www.networktechinc.com/environment-monitor-2d.html

 for the E-2D, and   

http://www.networktechinc.com/environment-

monitoring.html

  for the E-MINI-LXO.  

http://www.networktechinc.com/environment-monitor-micro.html

 for the E-MICRO-T(RHP) 

Manuals for each Environment Monitoring System covering installation and configuration for all features can also be found at 
these websites.    This manual is only provided to instruct how to connect the various sensors to these systems. 

 

CONNECT SENSORS TO E-MINI-LXO /-MICRO-T(RHP) 

 

E-T or TRHM-E7 

 

For measuring temperature and humidity, the E-MINI-LXO and E-MICRO-T(RHP) uses the E-T-E7 (temperature only),  E-TRHM-
E7 (combination temperature and humidity sensor).   For high-temperature environments, E-MINI-IND uses the E-T-IND-E7 High 
Temperature Sensor. 

1.  Connect either of the temperature / humidity sensors to an available port on the E-MINI-LXO.   Plug the RJ45 connector 

to either of the two ports marked "TEMPERATURE/HUMIDITY".  The E-T/TRHM-E7 sensors can be secured anywhere 
that the temperature and/or relative humidity need to be sensed.    

Note: The E-TRHM-E7 sensor will work with the E-MINI-LXO provided firmware version 2.3 or later is installed,   and with 
the E-MICRO provided firmware version 1.3 or later is installed.  

 
2.  Power-cycle the E-MINI-LXO after the sensor(s) have been plugged-in.  
 

Note: Mounting the sensor in the path of a fan or on a heated surface may affect the accuracy of the sensor’s readings

.  

Note: For best results, use the E-T-IND-E7 with model E-MINI-IND. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                  Figure 1- Connect sensors to E-MINI-LXO 

To extend a sensor cable (up 
to 500 feet long) requires  E-
MINI-LXO firmware version 2.0 
or later.  

Summary of Contents for ENVIROMUX E-BCN-R

Page 1: ...Date 5 7 2018 Sensor Installation Manual ENVIROMUX Series E T TRHM E7 Temperature Humidity sensors E LDSx y Liquid Detection Sensor E BCN R Beacon E SRN M Siren E M DCS3 Door Contact Switch E TDS Tam...

Page 2: ...e Alert Fix 11 TABLE OF FIGURES Figure 1 Connect sensors to E MINI LXO 2 Figure 2 Liquid detection sensor 4 Figure 3 Terminal block for dry contact sensors 5 Figure 4 Sensors connected by cables with...

Page 3: ...MICRO T RHP E T or TRHM E7 For measuring temperature and humidity the E MINI LXO and E MICRO T RHP uses the E T E7 temperature only E TRHM E7 combination temperature and humidity sensor For high tempe...

Page 4: ...n a 2 25 F 1 25 C Sensor Cable The CAT5 connection cable between the E MINI LXO E MICRO T RHP and the RJ45 Sensors is terminated with RJ45 connectors and must be wired according to the EIA TIA 568 B i...

Page 5: ...oblems after you have cleaned it with isopropyl alcohol or if you think the rope needs a good scrubbing you can clean it with warm soapy water You will have to remove the rope from its installed locat...

Page 6: ...h E M DCS3 Door Contact Sensor E DCS PS2 Plunger Style Door Contact Sensor To install the dry contact sensor s A Attach the positive lead to a terminal corresponding to a marking on the E MINI LXO and...

Page 7: ...ing temperature and humidity sensors to the ENVIROMUX the web interface will identify the sensor accordingly for the type of sensor it is The status bar and configuration page will enter the maximum a...

Page 8: ...ensors for plug in to the RJ45 Sensor sockets the following socket to sensor wiring must be followed RJ45 Sensor Socket Pinout Pin Pin Name 1 GND 2 SENSE 3 RS485 4 5 VDC 5 TAMPER SWITCH 6 RS485 7 12 V...

Page 9: ...NTI ENVIROMUX SENSOR INSTALLATION 8 Figure 8 Basic DIGITAL IN Terminal Connections...

Page 10: ...sure to only apply tape to the ends exposing as much of the sensor as possible At least 5 8 of the sensor must be exposed for it to function See Figure 2 Figure 9 Secure liquid detection sensor with t...

Page 11: ...tention All devices must be installed using 16 26 AWG wire Figure 11 Connect visual and audible external indicators For a complete listing of available sensors and accessories go to the product page f...

Page 12: ...Problem Receiving false alert messages from installed ENVIROMUX Liquid Detection sensor E LDx y or E LD LCx y Cause Sensor is in environment with significant electrical noise and is picking up this no...

Page 13: ...a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written consent of Network Technologies Inc 1275 Danner Drive...