This technique is also useful in testing the interaction of relays with Fire Alarm Control Panels, and
other systems, without having to do on-site smoke/flame/thermal testing.
Observing Smoke/Flame/Thermal detections using Enterprise Observer
As well as viewing normal live video from FireVu detectors Enterprise Observer can also display the
smoke, flame and high temperature events themselves as coloured rectangles overlaid on to the
video images of the detectors. These coloured rectangles represent the 16 detection zones of the
detector.
The colour key for these rectangles is as follows:
Smoke Detection:
Yellow:
Smoke detection in region.
Orange:
Smoke detection in region and Zone Wait time exceeded but Zone Vote not
reached.
Red:
Smoke detection in region and Zone Wait time exceeded and Zone Vote reached. A
smoke alarm is generated when this condition occurs.
Flame Detection:
Cyan:
Black body colour match and awareness count > 0 (movement detected) but
awareness threshold not yet met.
Magenta:
Flame detected. A flame alarm is generated if this condition occurs.
High Temperature Detection: