Page 25 of 97
Title FireVu Detector Standalone Installation Manual
NetVu Ltd.
No 1 Thellow Heath Park, Northwich Road, Northwich, Cheshire. CW9 6JB
Relay Outputs and Alarm Inputs
Four non-polarised solid-state relay outputs are provided.
Relay Outputs 2
–
4 are capable of switching 600mA at 60VDC.
Relay Output is 5 capable of switching 2.2A @60Vdc.
Relay Outputs 2 and 3 are also configurable for Loop Monitored fire loop alarms (see following
section for configuration)
Two Alarm Inputs are provided. These are logic level inputs, single ended.
ETHERNET CONNECTION
BROWN
WHITE/BROWN
GREEN
WHITE/GREEN
ORANGE
WHITE/ORANGE
BLUE
WHTE/BLUE
12VDC/24VDC
POWER
SUPPLY
+
_
CCTV TEST MONITOR
VIDEO
OUTPUT
RELAY
O/P 4
ALARM
I/P 1
ALARM
I/P 2
RELAY
O/P 3
RELAY
O/P 2
RELAY
O/P 5
GND
GND
GND
ALARM INPUTS
LEFT TO RIGHT
ALARM INPUT #1
GROUND
ALARM IN PUT #2
GROUND
RELAY OUTPUTS
LEFT TO RIGHT
RELAY #5
RELAY #2
RELAY #3
RELAY #4
Configuring Relay Outputs #2 and #3
If desired relay outputs #2 and #3 can be configured as monitored loop outputs. In this mode,
should the connection to the Fire Alarm Control Panel (FACP) or other system become short circuit
or open circuit then both the FACP and the FireVu detector will be able to detect this fault and
report it.