TRICON
®
SmartTrol
™
Installation and Maintenance Guide
33
Chapter 10: Setting Up the SmartTrol™
Configure the SmartTrol™ using the keyboard on the front panel of the unit. Press the “D”
key to enter the Set Up Mode. In all cases, when “v” appears in the last position of the
display, you can press the "D" key to display additional choices. Press the “ENT” key to
select the choice displayed. (Refer to the Worksheet.)
Setting Up the Counter
This section provides information for setting up the Counter.
Press
Display
D
MENU (Displays 1 second).
DEV TYPv.
ENT
RTv CNTv.
D
K FACT A (Displays 1 second).
######## (Current value blinks).
CLR
0 (blinks).
Key in new Counter K Factor A from worksheet.
ENT
K FACT B (displays 1 second).
######## (Current value blinks).
CLR
0 (blinks).
Key in new Counter K Factor B from worksheet.
ENT
R0v SPv.
Press B for Reset to 0, press D for SET to Preset.
ENT
ATv MANv.
Press B for Automatic Reset, press D for Manual Reset.
ENT
DEC LOC.
Key in number for the appropriate decimal point location; decimal point appears at
the designated spot on the display.
ENT
SmartTrol returns to normal operating mode.
Table 8 – Setting Up the Counter