Neptronic TFCB24F3XYZ1 Specification And Installation Instructions Download Page 8

TFCB24F3XYZ1 

Specification & Installation Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step Display 

Description 

Values 

42 

C

 

Heating set point during no occupancy:

 

Display shows 

“no occ heating setpnt”

 and the value of the heating set 

point temperature during no occupancy period. Moon   and heating 
symbols are also displayed. 
Please select the heating set point temperature during no occupancy. 
The maximum value is restricted by the no occupancy cooling set point. 
(step # 43) 

Range: 10.0 to 40.0ºC [50 to 104ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 16.0ºC [61ºF]

 

43 

C

 

Cooling set point during no occupancy:

 

Display shows 

“no occ cooling setpnt”

 and the value of the cooling set 

point temperature during no occupancy period. Moon   and cooling 
symbols are also displayed. 
Please select the cooling set point temperature during no occupancy. 
The minimum value is restricted by the no occupancy heating set point. 
(step # 42) 

Range: 10.0 to 40.0ºC [50 to 104ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 28.0ºC [82ºF]

 

44 

 

Enable or disable anti-freeze protection:

 

Display shows 

“enable anti freeze protect”

.

 

You can enable or disable the Anti-freeze function. 
When enabled, if temperature drop to 4ºC [39ºF], heat and reheat will 
start even if thermostat is in OFF mode.  
Heat and reheat will stop when temperature reach 5ºC [41ºF]. 
 

 

Default value: 
Disable (NO) 

45 

 

Communication bauds rate: 

Display shows 

“adjust comport bauds rate”

 and the value of the baud 

rate in kBds. 
Select the desired bauds for communication.

 

Range: 9600, 19200, 38400 & 76800 
Default value: 9.6 kBds 

46 

 

Communication MS/TP MAC address: 

Display shows 

“adjust MSTP Mac address”

Select the desired MS/TP Mac for communication.

 

Range: 0 to 254 
Increment: 1 
Default value: 1 

47 

 

Communication device instance:

 

Display shows 

“adjust device instanc 0153000”

If you want to change the device, select 

“yes”

 and go to next step. 

 

If you do not want to change the device, go directly to step #1. 

 

 Default value: no

 

48 

  

Communication device instance (cont’d):

 

Display shows the device address value. 
You can modify the device address by incrementing or decrementing the 

blinking digit with 

 or 

 buttons. To modify following digit on right press 

, to return to digit on the left press 

.  

Range: 0 to 4194302 
Increment: 1 by digit 

Default value: 0153000

 

 

Summary of Contents for TFCB24F3XYZ1

Page 1: ...2 F Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Presentation SEC VDC HR C F RH MAX V MIN V AM PM Symbols on display Cooling ON 33 66 10...

Page 2: ...on off or pulse heat 4 Pipe on off or pulse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local re...

Page 3: ...y the minimum value step 2 Maximum range 10 0 to 40 0 C 50 to 104 F Increment 0 5 C 1 F Default value 30 0 C 86 F 4 Locking the set point Display shows user setpnt locked and the status of the functio...

Page 4: ...y cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normal...

Page 5: ...minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which...

Page 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0 C 0 6 to 1...

Page 7: ...d Please select the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 External sensor selection Display shows extern sensor temper Please select whi...

Page 8: ...isplay shows enable anti freeze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4 C 39 F heat and reheat will start even if thermostat is in OFF mode Hea...

Page 9: ...e increased as per the setting made in programming mode If not locked no occupancy mode can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of derogation th...

Reviews: