Neptronic TFCB24F3XYZ1 Specification And Installation Instructions Download Page 4

TFCB24F3XYZ1 

Specification & Installation Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step Display 

Description 

Values 

 

Set signal for 2 pipe system:

 

Display shows 

“select 2 pipe signal”

.

 Cooling and heating symbols are 

also displayed.

 

Select which signal output you want for your 2 pipe system. 
You can choose analog, on/off or floating output. 
If you select analog, 

AO1

 will be set in automatic heat/cool change over. 

If you select on/off, 

TO1

 will be set in automatic heat/cool change over. 

If you select floating, 

TO1

 will be set close and 

TO2

 open. 

If you have selected analog signal, go directly to step #11. 
If you have selected on/off signal, go directly to step #13. 

 

 

Default value: Analog

 

10 

 

Set floating time:

 

Display shows 

“set floating time in seconds”

 and the floating time value 

(in seconds).

 

 

Please select desired value of the floating time signal.  
 

Go to step #13. 

Range: 15 to 250 seconds 
Increment: 5 seconds 

Default value: 100 seconds

 

11 

 

Minimum voltage of the analog output: 

Display shows 

“min vdc analog output”

 and the value of the minimum 

voltage of the analog ramp. 
Please select the desired value of the minimum voltage of the analog 
ramp. (This is the “zero” value) 
 
The minimum value is restricted by the maximum value. (step #11) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 0.0 Volt

 

12 

 

Maximum voltage of the analog output: 

Display shows 

“max vdc analog output”

 and the value of the minimum 

voltage of the analog ramp. 
Please select the desired value of the maximum voltage of the analog 
ramp. (This is the “span” value) 
 
The maximum value is restricted by the minimum value. (step #10) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 10.0 Volt

 

13 

 

Change over sensor selection:

 

Display shows 

“Ch over temper sensor”

Please select which sensor is rewired to the analog input: SENs (external 
change over sensor), NoCl (change over contact normally cool) or NoHt 
(change over contact normally heat). 
When normally cool “

NoC

L

” is selected, if contact is closed heating mode 

will be activated, if contact is opened cooling mode will be activated. 
When normally heat “

NoHt

” is selected, if contact is closed cooling mode 

will be activated, if contact is opened heating mode will be activated. 
When change over external sensor “

SENs

” is selected, heating mode will 

be activated when temperature read by external sensor is above the 
Change Over Set Point temperature, and cooling mode will be activated 
when temperature read by external sensor is under, 

see step #14.

 

If “SENs” is not selected, go directly to step #21.

 

 

 

Default value: SENs

 

14 

C

 

Change over set point temperature:

 

(If ‘’

SENs

’’ has been selected at step #13)

 

Display shows 

“Ch over setpnt temper”

 and the change over set point 

temperature. 
Please select the change over set point temperature. 
Note: heating mode will be activated when temperature read by external 
sensor is above the change over set point temperature, and cooling mode 
will be activated when temperature read by external sensor is under. 

Go to step #21.

 

Range: 10.0 to 40.0ºC [50 to 104ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 24.0ºC [82ºF]

 

15 

 

Set signal for 4 pipe heating system:

 

(If ‘’

4P

’’ has been selected at step #8)

 

Display shows 

“select 4 pipe heating signal”

.

 Heating symbols is also 

displayed.

 

Select which heating signal output you want for your 4 pipe system. 
You can choose analog, on/off or pulse output. 
If you select analog, 

AO2

 will be set in heating. 

If you select on/off or pulse, 

TO2

 will be set in heating. 

If you have selected on/off or pulse signal, go directly to step #18. 

Default value: 
Analog

 

16 

 

Minimum voltage of the heating output: 

Display shows 

“min vdc analog output heating”

 and the value of the 

minimum voltage of the heating ramp. 

 

Please select the desired value of the minimum voltage of the heating 
ramp. (This is the “zero” value) 
 
The minimum value is restricted by the maximum value. (step #17) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 0.0 Volt

 

Summary of Contents for TFCB24F3XYZ1

Page 1: ...2 F Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Presentation SEC VDC HR C F RH MAX V MIN V AM PM Symbols on display Cooling ON 33 66 10...

Page 2: ...on off or pulse heat 4 Pipe on off or pulse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local re...

Page 3: ...y the minimum value step 2 Maximum range 10 0 to 40 0 C 50 to 104 F Increment 0 5 C 1 F Default value 30 0 C 86 F 4 Locking the set point Display shows user setpnt locked and the status of the functio...

Page 4: ...y cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normal...

Page 5: ...minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which...

Page 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0 C 0 6 to 1...

Page 7: ...d Please select the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 External sensor selection Display shows extern sensor temper Please select whi...

Page 8: ...isplay shows enable anti freeze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4 C 39 F heat and reheat will start even if thermostat is in OFF mode Hea...

Page 9: ...e increased as per the setting made in programming mode If not locked no occupancy mode can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of derogation th...