TFCB24F3XYZ1 

Specification & Installation Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step Display 

Description 

Values 

25 

C

 

Reheat dead band: 

Display shows 

“control dead band reheat”

 and the value of the reheat 

dead band, heating symbol is also displayed. 
Please select the desired value of reheat dead band.

 

Dead band range:  

0.3 to 5.0ºC [0.6 to 10.0ºF] 

Increment: 0.1ºC [0.2ºF] 

Default value: 0.3ºC [0.6ºF]

 

26 

C

 

Proportional band in heating:

 

Display shows 

“control ramp HEATing”

 and the value of the heating 

proportional band, heating symbol is also displayed. 
Please select the desired value of heating proportional band.

 

Proportional band range:  

0.5 to 5.0ºC [1 to 10ºF] 

Increment: 0.5ºC [1ºF] 

Default value: 2.0ºC [4ºF] 

27 

C

 

Proportional band in cooling:

 

Display shows 

“control ramp cooling”

 and the value of the cooling 

proportional band, cooling symbol is also displayed. 
Please select the desired value of cooling proportional band. 

Proportional band range:  

0.5 to 5.0ºC [1 to 10ºF] 

Increment: 0.5ºC [1ºF] 

Default value: 2.0ºC [4ºF]

 

28 

C

 

Dead band in heating: 

Display shows 

“control dead band heating”

 and the value of the heating 

dead band, heating symbol is also displayed. 
Please select the desired value of heating dead band.

 

Dead band range:  

0.3 to 5.0ºC [0.6 to 10.0ºF] 

Increment: 0.1ºC [0.2ºF] 

Default value: 0.3ºC [0.6ºF]

 

29 

C

 

Dead band in cooling: 

Display shows 

“control dead band cooling”

 and the value of the cooling 

dead band, cooling symbol is also displayed. 
Please select the desired value of cooling dead band. 

Dead band range:  

0.3 to 5.0ºC [0.6 to 10.0ºF] 

Increment: 0.1ºC [0.2ºF] 

Default value: 0.3ºC [0.6ºF]

 

30 

 

Anti-cycling delay cooling contact (protection for compressor):

Display shows 

“cooling anti cycle minutes”

 and the value (in minutes) of 

the delay to activate / reactivate cooling contact. 
Please select the desired value of the delay cooling contact.

 

Range: 0 to 15 min. 
Increment: 1 min. 

Default value: 2 min.

 

31 

 

Integration time factor setting: 

Display shows 

“adjust intgral time in seconds”

 and the time in seconds 

for the integration factor compensation. 
Please select the desired value of the integration factor compensation. 

Range: 0 to 250 seconds 
Increment: 5 seconds 

Default value: 0 second

 

32 

 

Fan damping factor setting:

Display shows 

“adjust damping factor seconds”

 and the time in 

seconds for the damping factor which will slow down the effect in change 
of demand for fan speed. 
Please select the desired value of the damping factor. 

Range: 0 to 10 seconds 
Increment: 1 second 

Default value: 0 second

 

33 

 

Fan speed signal: 

Display shows 

“select fan speed signal”

 

and the speed of the fan. Fan 

symbol is also displayed. 
Select which fan speed signal or quantity of contact you want: Analog 
signal, 1 speed, 2 speed or 3 speed. 
 

If you want to use 1, 2 or 3 fan contacts, select speed desired and go 
directly to step #36. 

 

 

 

Default value: 3 speed fan contact

Summary of Contents for TFCB24F3XYZ1

Page 1: ...2 F Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Presentation SEC VDC HR C F RH MAX V MIN V AM PM Symbols on display Cooling ON 33 66 10...

Page 2: ...on off or pulse heat 4 Pipe on off or pulse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local re...

Page 3: ...y the minimum value step 2 Maximum range 10 0 to 40 0 C 50 to 104 F Increment 0 5 C 1 F Default value 30 0 C 86 F 4 Locking the set point Display shows user setpnt locked and the status of the functio...

Page 4: ...y cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normal...

Page 5: ...minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which...

Page 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0 C 0 6 to 1...

Page 7: ...d Please select the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 External sensor selection Display shows extern sensor temper Please select whi...

Page 8: ...isplay shows enable anti freeze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4 C 39 F heat and reheat will start even if thermostat is in OFF mode Hea...

Page 9: ...e increased as per the setting made in programming mode If not locked no occupancy mode can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of derogation th...

Reviews: