TFCB24F3XYZ1
Specification & Installation Instructions
6
Step Display
Description
Values
25
C
Reheat dead band:
Display shows
“control dead band reheat”
and the value of the reheat
dead band, heating symbol is also displayed.
Please select the desired value of reheat dead band.
Dead band range:
0.3 to 5.0ºC [0.6 to 10.0ºF]
Increment: 0.1ºC [0.2ºF]
Default value: 0.3ºC [0.6ºF]
26
C
Proportional band in heating:
Display shows
“control ramp HEATing”
and the value of the heating
proportional band, heating symbol is also displayed.
Please select the desired value of heating proportional band.
Proportional band range:
0.5 to 5.0ºC [1 to 10ºF]
Increment: 0.5ºC [1ºF]
Default value: 2.0ºC [4ºF]
27
C
Proportional band in cooling:
Display shows
“control ramp cooling”
and the value of the cooling
proportional band, cooling symbol is also displayed.
Please select the desired value of cooling proportional band.
Proportional band range:
0.5 to 5.0ºC [1 to 10ºF]
Increment: 0.5ºC [1ºF]
Default value: 2.0ºC [4ºF]
28
C
Dead band in heating:
Display shows
“control dead band heating”
and the value of the heating
dead band, heating symbol is also displayed.
Please select the desired value of heating dead band.
Dead band range:
0.3 to 5.0ºC [0.6 to 10.0ºF]
Increment: 0.1ºC [0.2ºF]
Default value: 0.3ºC [0.6ºF]
29
C
Dead band in cooling:
Display shows
“control dead band cooling”
and the value of the cooling
dead band, cooling symbol is also displayed.
Please select the desired value of cooling dead band.
Dead band range:
0.3 to 5.0ºC [0.6 to 10.0ºF]
Increment: 0.1ºC [0.2ºF]
Default value: 0.3ºC [0.6ºF]
30
Anti-cycling delay cooling contact (protection for compressor):
Display shows
“cooling anti cycle minutes”
and the value (in minutes) of
the delay to activate / reactivate cooling contact.
Please select the desired value of the delay cooling contact.
Range: 0 to 15 min.
Increment: 1 min.
Default value: 2 min.
31
Integration time factor setting:
Display shows
“adjust intgral time in seconds”
and the time in seconds
for the integration factor compensation.
Please select the desired value of the integration factor compensation.
Range: 0 to 250 seconds
Increment: 5 seconds
Default value: 0 second
32
Fan damping factor setting:
Display shows
“adjust damping factor seconds”
and the time in
seconds for the damping factor which will slow down the effect in change
of demand for fan speed.
Please select the desired value of the damping factor.
Range: 0 to 10 seconds
Increment: 1 second
Default value: 0 second
33
Fan speed signal:
Display shows
“select fan speed signal”
and the speed of the fan. Fan
symbol is also displayed.
Select which fan speed signal or quantity of contact you want: Analog
signal, 1 speed, 2 speed or 3 speed.
If you want to use 1, 2 or 3 fan contacts, select speed desired and go
directly to step #36.
Default value: 3 speed fan contact