Neptronic TFCB24F3XYZ1 Specification And Installation Instructions Download Page 7

TFCB24F3XYZ1 

Specification & Installation Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step Display 

Description 

Values 

34 

 

Minimum voltage of the fan output: 

Display shows 

“min vdc analog output fan”

 and the value of the 

minimum voltage of the fan ramp. 
Please select the desired value of the minimum voltage of the fan ramp. 
(This is the “zero” value) 
 
The minimum value is restricted by the maximum value. (step #35) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 0.0 Volt

 

35 

 

Maximum voltage of the fan output:

Display shows 

“max vdc analog output fan”

 and the value of the 

minimum voltage of the fan ramp. 
Please select the desired value of the maximum voltage of the fan ramp. 
(This is the “span” value) 
 
The maximum value is restricted by the minimum value. (step #34) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 10.0 Volt

 

36 

 

Set fan speed automatic mode enable or disable:

  

Display shows 

“enable fan auto mode”

. Fan   symbol is also displayed. 

You can enable or disable the Automatic mode adjustment by end user.  
 

If you selected to disable the automatic mode, go directly to step 
#38.

 

 

Default value: 
Enable (YES)

 

37 

 

Time out fan contact: 

Display shows 

“fan auto timeout minutes”

 and the automatic shutoff delay 

value (in minutes) when there is no demand.

 

Please select the desired value of the automatic shutoff delay. 

Range: 0 to 15 min. 
Increment: 1 min. 

Default value: 2 min.

 

38 

 

External sensor selection:

 

Display shows 

“extern sensor temper”

Please select which sensor is rewired to the analog input: OFF (input 
none rewired), t10.0 (external temperature sensor 10.0

 

K

When nothing “

OFF

” is selected, the thermostat is controlled by is 

internal temperature sensor. 
When external sensor “

t10.0

” is selected, the thermostat is controlled by 

an external temperature sensor. 

If you have selected OFF, go directly to step #40.

 

  

Default value: Off

 

39 

C

 

External temperature sensor calibration:

 

Display shows 

“extern temper sensor offset”

 and temperature read by 

external temperature sensor. 
If the sensor is not connected or short circuited, the display shows 

Eror

.

You can adjust the calibration of the external sensor by comparison with a 
known thermometer. 

Range: 0.0 to 50.0ºC [41.0 to 122.0ºF] 
  

(max. offset ± 5 ºC) 

Increment: 0.1ºC [0.2ºF] 

40 

 

Occupancy contact:

 

Display shows 

“Select occ contact”

. Moon   symbol is also displayed. 

You can choose NO (normally open) or NC (normally close) contact. 

 

Default value: 
Normally open (NO)

 

41 

 

No occupancy derogation time :

 

Display shows 

“no occ delay overide minutes”

 and the derogation time in 

minute. NSB   symbol is also displayed. 
Please select the desired derogation time. 
If no derogation time is desired select “0”. 
 

Range: 0 to 180 min. 
Increment: 15 min. 

Default value: 120 min.

 

Summary of Contents for TFCB24F3XYZ1

Page 1: ...2 F Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Presentation SEC VDC HR C F RH MAX V MIN V AM PM Symbols on display Cooling ON 33 66 10...

Page 2: ...on off or pulse heat 4 Pipe on off or pulse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local re...

Page 3: ...y the minimum value step 2 Maximum range 10 0 to 40 0 C 50 to 104 F Increment 0 5 C 1 F Default value 30 0 C 86 F 4 Locking the set point Display shows user setpnt locked and the status of the functio...

Page 4: ...y cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normal...

Page 5: ...minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which...

Page 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0 C 0 6 to 1...

Page 7: ...d Please select the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 External sensor selection Display shows extern sensor temper Please select whi...

Page 8: ...isplay shows enable anti freeze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4 C 39 F heat and reheat will start even if thermostat is in OFF mode Hea...

Page 9: ...e increased as per the setting made in programming mode If not locked no occupancy mode can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of derogation th...

Reviews: