Neptronic TFCB24F3XYZ1 Specification And Installation Instructions Download Page 5

TFCB24F3XYZ1 

Specification & Installation Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step Display 

Description 

Values 

17 

 

Maximum voltage of the heating output: 

Display shows 

“max vdc analog output heating”

 and the value of the 

minimum voltage of the heating ramp. 
Please select the desired value of the maximum voltage of the heating 
ramp. (This is the “span” value) 
 
The maximum value is restricted by the minimum value. (step #16) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 10.0 Volt

 

18 

 

Set signal for 4 pipe cooling system:

 

(If ‘’

4P

’’ has been selected at step #8)

 

Display shows 

“select 4 pipe cooling signal”

.

 Cooling symbols is also 

displayed.

 

Select which cooling signal output you want for your 4 pipe system. 
You can choose analog or on/off output. 
If you select analog, 

AO1

 will be set in cooling. 

If you select on/off, 

TO1

 will be set in cooling. 

If you have selected on/off signal, go directly to step #21. 

 

Default value: Analog

 

19 

 

Minimum voltage of the cooling output: 

Display shows 

“min vdc analog output cooling”

 and the value of the 

minimum voltage of the cooling ramp. 
Please select the desired value of the minimum voltage of the cooling 
ramp. (This is the “zero” value) 
 
The minimum value is restricted by the maximum value. (step #20) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 0.0 Volt

 

20 

 

Maximum voltage of the cooling output: 

Display shows 

“max vdc analog output cooling”

 and the value of the 

minimum voltage of the cooling ramp. 
Please select the desired value of the maximum voltage of the cooling 
ramp. (This is the “span” value) 
 
The maximum value is restricted by the minimum value. (step #19) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 10.0 Volt

 

21 

 

Set local reheat signal 

Display shows 

“set local reheat signal”

.

 Heating symbols is also 

displayed.

 

Select which signal output you want for reheat. 
 
You can choose OFF (no signal selected), ANALOG heating only, 
ANALOG heating & fan, ON/OFF heating only, ON/OFF heating & fan, 
PULSE heating only, PULSE heating & fan output. 
 
If you select analog (& fan), 

AO3

 will be set in reheat. 

If you select on/off (& fan) or pulse (& fan), 

TO3

 will be set in reheat. 

 

If you have selected analog (& fan) signal, go directly to step #22. 
If you have selected on/off (& fan) or pulse (& fan) signal, go directly 
to step #24. 
If you have selected OFF, go directly to step #26.

 

 

 

 

 

 

 

Default value: Off

 

22 

 

Minimum voltage of the reheat output:

Display shows 

“min vdc analog output reheat”

 and the value of the 

minimum voltage of the reheat ramp. 
Please select the desired value of the minimum voltage of the reheat 
ramp. (This is the “zero” value) 
 
The minimum value is restricted by the maximum value. (step #23) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 0.0 Volt

 

23 

 

Maximum voltage of the reheat output: 

Display shows 

“max vdc analog output reheat”

 and the value of the 

minimum voltage of the reheat ramp. 
Please select the desired value of the maximum voltage of the reheat 
ramp. (This is the “span” value) 
 
The maximum value is restricted by the minimum value. (step #22) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 10.0 Volt

 

24 

C

 

Reheat proportional band:

 

Display shows 

“control ramp reheat”

 and the value of the reheat 

proportional band, heating symbol is also displayed. 
Please select the desired value of reheat proportional band.

 

Proportional band range:  

0.5 to 5.0ºC [1 to 10ºF] 

Increment: 0.5ºC [1ºF] 

Default value: 2.0ºC [4ºF] 

Summary of Contents for TFCB24F3XYZ1

Page 1: ...2 F Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Presentation SEC VDC HR C F RH MAX V MIN V AM PM Symbols on display Cooling ON 33 66 10...

Page 2: ...on off or pulse heat 4 Pipe on off or pulse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local re...

Page 3: ...y the minimum value step 2 Maximum range 10 0 to 40 0 C 50 to 104 F Increment 0 5 C 1 F Default value 30 0 C 86 F 4 Locking the set point Display shows user setpnt locked and the status of the functio...

Page 4: ...y cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normal...

Page 5: ...minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which...

Page 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0 C 0 6 to 1...

Page 7: ...d Please select the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 External sensor selection Display shows extern sensor temper Please select whi...

Page 8: ...isplay shows enable anti freeze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4 C 39 F heat and reheat will start even if thermostat is in OFF mode Hea...

Page 9: ...e increased as per the setting made in programming mode If not locked no occupancy mode can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of derogation th...

Reviews: