Networkable VAV Controller

Specification and Installation Instructions

 

EVCB14-TRL-TDU-180315

 

 

Page | 1 

Controller Models 

EVCB14NIT0S 

 

(0 TRIACS / pressure independent) 

EVCB14NIT2S  

(2 TRIACS / pressure independent) 

EVCB14NIT4S  

(4 TRIACS / pressure independent) 

EVCB14NDT4S

 

(4 TRIACS / pressure dependent) 

EVCB14NIT0SF

 

(0 TRIACS / independent / feedback) 

EVCB14NIT4SF

 

(4 TRIACS / independent / feedback) 

TRL Series Thermostat 

TRL24   

 

 

(Thermostat 2x4) 

TRLH24

   

 

 

(Thermostat 2x4 with Humidity) 

TRLG24

   

 

 

(Thermostat 2x4 with CO

2

TRLGH24   

 

(Thermostat 2x4 with CO

2

 and Humidity) 

TDU Series Thermostat 

TDU10   

 

 

(Grey LCD, white enclosure)

 

TDU40   

 

 

(Black LCD, black enclosure)

 

TDU70   

 

 

(Black LCD, white enclosure)

 

 

EVCB Series 

 

TRL24 Series 

 

TDU10 / TDU40 / TDU70 Series 

Description 

The EVCB Series is a combination controller and thermostat 
with support for networked communications via the BACnet 
MS/TP or Modbus protocol. The EVCB Series controller is 
compatible with both TRL24 and TDU series thermostats. The 
Networkable VAV Controller is designed for simple and 
accurate control of any variable air volume box in a number of 
zone control configurations. Its field configurable algorithms 
enable versatile implementation of required control sequences.  

Applications 

 

Single duct, cooling only 

 

Single duct cooling and/or heating 

 

Up to 4 stage reheat and/or cool 

 

Up to 4 On/Off heat and/or cool 

 

Up to 4 time proportioned (TPM) heat or reheat 

 

Up to 2 analog (0-10Vdc) reheat and/or cool 

 

Up to 2 floating heat and/or cool 

 

Pressure dependent or pressure independent 

 

With or without auto changeover 

 

Supply/exhaust (requires an additional EVC) 

Features 

 

Field configured VAV algorithms, inputs and outputs 

 

Built-in actuator, 70 lb-in  

 

On board differential pressure sensor (select models) 

 

Select direction on analog outputs 

 

Simple air balancing and commissioning via thermostat 

 

Automatically sets operation mode to pressure dependent 
or independent based on the presence of air flow  

 

Configurable PI (Proportional-Integral) function 

 

Independent, configurable proportional control band and 
dead band per ramp 

 

Selectable internal or external temperature sensor (10KΩ) 

 

Activate output with CO

2

 sensor from TRL/TDU or external 

sensor input 

 

Changeover by contact or external temperature sensor 

 

Internal and external temperature sensor calibration 

 

Optional potentiometer feedback for increased precision of 
actuator position 

 

Freeze protection 

 

Removable, raising clamp, non-strip terminals 

Operational Features 

 

Backlit LCD with simple icon and text driven menus 

 

Select thermostat’s default display 

 

Network service port via on-board mini USB connector 

 

Manual night setback or no occupancy override 

 

Multi level lockable access menu and setpoint 

 

Selectable Fahrenheit or Celsius scale  

 

3-wire connection to controller and 4 push buttons 

Network Communication 

 

BACnet MS/TP or Modbus communication port  

 

Select MAC address via DIP switch or via network 

 

Automatic baud rate detection 

BACnet MS/TP® 

 

Automatic device instance configuration 

 

Copy & broadcast configuration via thermostat menu or via 
BACnet to other controllers 

 

BACnet scheduler 

 

Firmware upgradeable via BACnet 

 

Support COV (change of value) 

Modbus 

 

Modbus @ 9600, 19200, 38400 or 57600 bps 

 

RTU Slave, 8 bits (configurable parity and stop bits) 

 

Connects to any Modbus master 

 

 

Summary of Contents for EVCB14NDT4S

Page 1: ...angeover Supply exhaust requires an additional EVC Features Field configured VAV algorithms inputs and outputs Built in actuator 70 lb in On board differential pressure sensor select models Select dir...

Page 2: ...0 C to 50 C 32 F to 122 F Storage temperature 30 C to 50 C 22 F to 122 F Relative Humidity 5 to 95 non condensing Weight 1 8 kg 4 lb The actuator performs an auto stroke on power up When changing the...

Page 3: ...ls Model Temp RH CO2 PIR Color TDU10 100 grey LCD white enclosure TDU10 101 TDU10 102 TDU10 103 TDU10 104 TDU10 105 TDU10 106 TDU10 107 TDU10 Series Model Temp RH CO2 PIR Color TDU40 100 black LCD bla...

Page 4: ...C Celsius Scale F Fahrenheit Scale RH Humidity A Automatic Mode Cooling Heating Fan Mechanical Installation Actuator 1 Manually close the damper blades and position the actuator to 0 or 90 2 Slide the...

Page 5: ...riate connections D Mount the thermostat onto the wall plate To mount the thermostat correctly place the top of the thermostat on the mounting plate first and push it into the grooves to snap it into...

Page 6: ...M 2 digital inputs config DI2 Override normally cool heat DI1 OCC open close NSB open close 3 2 1 COM 24Vac input TO2 TO1 TO1 4 TO2 7 6 5 COM 24Vac input TO3 TO4 TO3 8 TO4 4 TRIAC outputs config Cool...

Page 7: ...er the action button or the button used to access the menus and save changes is different in the thermostats Use the following menu overviews with the appropriate action button as per your thermostat...

Page 8: ...Configuration ON enabled Pressur Mode Auto Change OFF disabled Motor Minimum Pos Cooling 10 0 100 Motor Minimum Pos Heating 10 0 100 ClHt cool heat Control Apps Cl cool only scroll menu items APPS AP...

Page 9: ...10Vdc AI2 Signal Type EtS external temp sensor OFF disabled NoHt normally heat NoCl normally cool SENs sensor CH Over Setpnt 24 C select set value AI2 CO2 Maximum Range 2000 ppm CO2 Setpnt 800 ppm Go...

Page 10: ...llows demand CO2 carbon dioxide Hr2 heating ramp 2 Hr1 heating ramp 1 Cr2 cooling ramp 2 Cr1 cooling ramp 1 TO2 Ramp OFF select set value MSV 27 TO2 Go to TO1 Close Percent Go to TO1 DIR REV OPt Optio...

Page 11: ...mum Voltage 0 0 Vdc Go to tmp AO2 Maximum Voltage 10 0 Vdc Go to tmp Main Menu Sub Menu Configuration AO1 AO2 TO4 TO3 TO2 Output Config TO1 scroll menu items scroll menu items MSV 20 MSV 22 AV 70 AV 7...

Page 12: ...0 F 0 5 5 C 1 9 F CR1 Dead Band 0 3 C 0 6 F 0 5 C 0 9 F CR2 Prop Band 2 0 C 4 0 F 0 5 5 C 1 9 F CR2 Dead Band 0 3 C 0 6 F 0 5 C 0 9 F Hr1 Prop Band 2 0 C 4 0 F 0 5 5 C 1 9 F Hr1 Dead Band 0 3 C 0 6 F...

Page 13: ...in in progress Go to HrS Copy Config Result Succeed Go to HrS select set value Hours 12 0 23 or 1 12 am pm Minutes 00 00 59 Year 15 15 99 Set Time Display format 24 24 hour format 12 AM PM format Mont...

Page 14: ...tS External temperature sensor When the thermostat is connected to the appropriate analog input the display shows the temperature read by the external temperature sensor Adjust the offset by comparing...

Page 15: ...inheat airflowto Kfactor Minimum Heating Airflow 200 0to max heat airflow Go to bAL Airflow Balance CLOs close Min minimum flow mA maximum flow OPEn fully opened Close Motor 130 see note Minimum Airfl...

Page 16: ...rough the following values Airflow Airflow Setpoint Actual Damper Pos Percent Air Supply Temp appears only in pressure independent mode appears only if AST is selected for the Analog Input Signal Type...

Page 17: ...emp After 5 seconds without any action the thermostat returns to operation mode The air supply temperature appears only if analog input AI1 or AI2 are configured with the AST option Not available on t...

Page 18: ...Type On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On O...

Page 19: ...Notes...

Page 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Reviews: