Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com
EVCB Standard
Page | 10
TRIAC Outputs – Menu (3 of 6) |
TO1 to TO4
On
(fan continuously on )
Auto
(fan follows demand )
TO1 DIR-REV
DIR
(direct )
REV
(reverse)
PuLs
(pulsed ) *
AO1
AO2
FLt
(floating )
CO2
(carbon dioxide )
Hr2
(heating ramp 2)
Hr1
(heating ramp 1)
TO4
TO3
TO2
Output Config
TO1
Cr2
(cooling ramp 2)
Cr1
(cooling ramp 1)
TO1 Ramp
OFF
= scroll menu items
= select / set value
TO1 Close Percent
40%
(15-80%)
TO1 Signal Type
OnOf
(on/off)
Go to "TO2"
* = Only if Hr1 or Hr2 is selected
TO1-TO2 Floating Time in Sec
100 sec
(15 to 250 /420 § secs)
TO1 Open Percent
0%
[0-(TO1 cls pos-4)]
Go to
"TO2"
TO2 DIR-REV
DIR
(direct )
REV
(reverse )
PuLs
(pulsed )
TO2 Close Percent
40%
(15-80%)
TO2 Signal Type
OnOf
(on/off)
Go to "TO3"
TO2 Open Percent
0%
[0-(TO2 cls pos-4)]
Go to
"TO3"
Main Menu
Sub Menu
Configuration
= scroll menu items
TO1-TO2 DIR-REV
DIR
(direct )
REV
(reverse)
Go to
"TO3"
MSV.25
MSV.26
MSV.28
AV.77
AV.75
AV.79
AV.78
BV.32
BV.30
AV.80
BV.33
If CO
2
was selected
ầ
= Auto and On options
are for fan powered box
applications and are only
available with models:
- EVCB14NIT4S
- EVCB14NDT4S
- EVCB14NIT4SF
Go to "TO2 Close Percent "
Go to "TO2 DIR-REV"
The number of Triac outputs
(TO) depend on the model .
S = motor/actuator.
TO(S) = None
T2(S) = 2
T4(S) = 4
TO1
On
(fan continuously on )
Auto
(fan follows demand )
CO2
(carbon dioxide )
Hr2
(heating ramp 2)
Hr1
(heating ramp 1)
Cr2
(cooling ramp 2)
Cr1
(cooling ramp 1)
TO2 Ramp
OFF
= select / set value
MSV.27
TO2
Go to "TO1 Close Percent "
Go to "TO1 DIR-REV"
OPt
(Options)
Only available with
CO
2
sensor models
Main Menu
APPS
(Applications)
PrSs
(Pressure)
rMp
(Ramps)
NET
(Network)
HrS
(Time & Date)
Setc
(Settings)
Mot
(Motor)
tMp
(Temperature )
OutP
(Outputs)
InPt
(Inputs)
TO3 Open Percent
TO3 Close Percent
TO3 DIR -REV
DIR
(direct )
REV
(reverse )
PuLs
(pulsed ) *
FLt
(floating )
40%
(15-80%)
TO3 Signal Type
OnOf
(on/off)
Go to "TO4"
* = Only if Hr1 or Hr2 is selected
TO3-TO4 Floating Time in Sec
100 sec
(15 to 250 /420§ secs)
TO4 DIR -REV
DIR
(direct )
REV
(reverse )
PuLs
(pulsed )
TO4 Close Percent
40%
(15-80%)
TO4 Signal Type
OnOf
(on/off)
Go to "AO1"
TO4 Open Percent
0%
[0-(TO4 cls pos-4)]
Go to
"AO1"
TO3-TO4 DIR -REV
DIR
(direct )
REV
(reverse )
MSV.30
MSV.32
AV.81
AV.76
AV.83
AV.82
AV.84
BV.31
BV.34
BV.35
If CO
2
was selected
Go to "TO3 Close Percent "
Go to "TO3 DIR-REV"
Go to "TO4 Close Percent "
Go to "TO4 DIR-REV"
On
(fan continuously on )
Auto
(fan follows demand )
CO2
(carbon dioxide )
Hr2
(heating ramp 2)
Hr1
(heating ramp 1)
Cr2
(cooling ramp 2)
Cr1
(cooling ramp 1)
TO3 Ramp
OFF
= select / set value
MSV.29
TO3
On
(fan continuously on )
Auto
(fan follows demand )
CO2
(carbon dioxide )
Hr2
(heating ramp 2)
Hr1
(heating ramp 1)
Cr2
(cooling ramp 2)
Cr1
(cooling ramp 1)
TO4 Ramp
OFF
= select / set value
MSV.31
TO4
0%
[0-(TO3 cls pos-4)]
Go to
"TO4"
Go to
"AO1"
*** To save any changes , press on TRL and on TDU ***