59
According to the device you use, choose the Analog Input in the second Drop-Down (temperature,
humidity, light, current, energy...).
Action Condition:
The options "higher than" and "lower than" enable you to define when the rule has to be executed.
- Choose "higher than" if you want to execute the rule when the environment value exceeds the value you
defined in the field on the right of "higher than".
- Choose "lower than" if you want to execute the rule when the environment value is below the value you
defined in the field on the right of "lower than".
•
For temperature, you can define values between -25°C and 60°C, +/- 2°C.
•
For relative humidity, you can define values between 20 RH and 80 RH, +/- 3%.
•
For ambient light, you can define values between 0 and 1000 Lux.
•
For the effective current (rms), you can define values between 1 and 10 Amps.
Configuring the Actions
For the Event defined above, you can choose and configure the following actions:
Set Group:
This type of action appears and can be configured only if you have already created at least one
group (Settings/Groups Tab).
Check this box and in the corresponding drop-down list choose the power outlet group the rule will apply
to. In the next corresponding drop-down list, choose the action to execute.
Each power outlet group can be switched On/Off and restarted. If you choose "restart" you will also be
able to define a restart delay between 0 and 65535 seconds.
- If you choose 0 second, the delay will be the delay defined in the ePowerSwitch power outlets settings.
- If you choose a delay different from 0, the delay will replace the delay defined in the ePowerSwitch
power outlets settings.
Set Power Outlet:
Check this box and in the corresponding drop-down list choose the power outlet the rule will apply to. In
the next corresponding drop-down list, choose the action to execute. Each power outlet can be switched
On/Off and restarted. If you choose "restart" you will also be able to define a restart delay between 0 and
65535 seconds.
- If you choose 0 second, the delay will be the delay defined in the ePowerSwitch power outlets settings.
- If you choose a delay different from 0, the delay will replace the delay defined in the ePowerSwitch
power outlets settings.
Set Digital Output:
Check this box and in the first corresponding drop-down list, choose the device from which one you want
to switch a digital output. In the second drop-down list, choose the digital output the rule will apply to. In
the next corresponding drop-down list, choose the action to execute. Each digital output can be open,
close, pulse open or pulse close. If you choose "pulse...", you will also be able to define a pulse delay
between 0 and 65535 seconds.
- If you choose 0 second, the delay will be the delay defined in the digital output settings.
- If you choose a delay different from 0, the delay will replace the delay defined in the digital output
settings.
Send Syslog Messages:
This type of action can be configured only if you have already created at least one destination
Syslog Server (Misc/Log Settings Tab).
Check this box if you want to send a message to a Syslog server. In the following drop-down lists choose
the facility and the severity of the message to send. The address of the Syslog server has to be defined in
the "Log Settings Page".