4.6.5 EN50160
This function allows the automatic evaluation according to EN50160 or other standards.
1) Select Limit and Percentile
After selecting the datafile(s) for power quality evaluation the limit values and
corresponding percentil can be selected or individually defined. Predefined templates are
available for EN50160, IEC61000-2-2, IEC61000-2-4, IEEE519, FoL standards. Other
templates can be added by oneself or by NEO Messtechnik.
2)
Select time-intervall
(Note: Multiple data files can be analysed together)
3)
Analysis and Report visualisations see:
The table shows all parameters and the limits according to EN50160. The limits may also be
applied to other limits (see IEC61000-2-4).
1) Limit:
Defined limit
2) Interval:
Defined time-interval for evaluation
3) MIN*/MAX/%Out:
MIN*…Minimal measured value
MAX…Maximal measured value
%Out…Number of samples out of limit