Page
38
of
76
4.5.6 EN50160 Analyzer
Navigation: “Advanced” – “EN50160”
The
EN50160 panel
shows Power Quality evaluation according to EN50160 standard.
It is possible to switch between the evaluation of all data and evaluation of not flagged
data (data when no voltage event occurred).
All quantities are measured and evaluated according to IEC 61000-4-30 class A.
A complex overview and also more event details can be displayed. The event details
include event distribution, rapid voltage changes distribution and rapid voltage changes
statistics. EN50160 events itself are displayed in the events list panel.
1. Selection of view type
– complex, events distribution, RVC Events and RVC statistics
2. Select Flagged/Not Flagged data for evaluation
3. Initialization button
4. Start time of evaluation
5. Voltage quality information
Limit: Limit Values defined by selected standard (EN50160, IEC61000-2-2, etc.)
Max/*Min: Max and Min values of evaluation period
Above/*Below: Samples above or below the limits
% OK: Percentage within range
Fit?: Indication if standard is fullfiled or not
For a more detailed description of the measured parameters according to the
EN50160 standard, we would like to refer to the Technical Reference Manual.
1
2
3
4
5
Summary of Contents for PQA8000