The controller has 4 separate, user-selectable sets of settings for configuring the RO. The factory default 

settings are shown below. The settings are identical except for variations in the flush behavior.
 • 

Program 1

High Pressure flush

 • 

Program 2

No Flush

 • 

Program 3

Permeate Flush, (low pressure, inlet valve closed)

 • 

Program 4

Low Pressure, feed water flush

See the previous page for instructions on how to access the menu for selecting these programs.
See Appendix A for a detailed explanation of the Parameters and their affect on the RO’s operation.

  Table 2 - Controller Programming:  

ROC2HE Program Selections

Parameter

Value

Program 1

Program 2

Program 3

Program 4

Tank Level Switch delay

 (actuation and de-actuation)

Seconds

2

2

2

2

Pressure Switch delay (actuation and de-actuation)

Seconds

2

2

2

2

Pretreat Switch delay (actuation and de-actuation) 

Seconds

2

2

2

2

Pump start delay

Seconds

10

10

10

10

Inlet Solenid stop delay

Seconds

1

1

1

1

Pump start retry interval (restart delay after LP fault)

Seconds

60

60

60

60

Low pressure fault shutdown, # of faults

Faults

5

5

5

5

Low pressure fault shutdown, time period to count faults

Minutes

10

10

10

10

Low pressure fault shutdown, reset after shutdown

Minutes

60

60

60

60

Low pressure time out fault

Seconds

60

60

60

60

Flush Behavior

High Pressure

No Flush

Perm Flush

Low Pres Flush

Startup Flush:

 Minutes from last flush

Minutes

0

0

0

0

Startup Flush:

 Duration 

Seconds

0

0

0

30

Periodic Flush:

 Interval

Minutes

60

0

0

Periodic Flush: 

Duration

Seconds

30

0

0

0

Shutdown Flush:

 Time from last flush

Minutes

10

0

0

0

Shutdown Flush:

 Minumum operation

Minutes

30

0

0

0

Shutdown Flush:

 Duration

Seconds

60

0

60

60

Idle Flush:

 Interval *

Minutes

0

0

0

0

Idle Flush:

 Duration *

Seconds

0

0

0

0

Timed Manual Run

Minutes

5

5

5

5

Timed Manual Flush

Seconds

5

0

5

5

*  These features are disabled by default due to the potential for confusion on the part of end-users in the field. 

They can be enabled when needed via the OEM PC programming interface which allows changes to all of 

the values shown above.

Summary of Contents for NRO ROC2HE-UL

Page 1: ...Nelsen NRO ROC2HE UL System Controller Documentation Systems w CPU 4 Control Board Manufactured after March 2020 Since 1954...

Page 2: ......

Page 3: ...Controller Detail TB 1 6 Conductivity Probe Installation Figure 5 7 Installation Instructions 7 Controller Programming Accessing Hidden Menus Figure 6 8 System Start up w Permeate Flush 8 Controller...

Page 4: ...0 6000 s standard sensor CP 1 K 75 Output Circuit Ratings Feed Solenoid 1A Voltage is the same as motor supply voltage Flush Solenoid 1A Voltage is the same as motor supply voltage Motor 1 0 HP 110 12...

Page 5: ...3 Figure 1 Simplified Schematic...

Page 6: ...ard CPU 4 Conductivity Probe Connections Display 4 line 20 character Clear concise feedback on the RO s status Alarm Display backlight flashes along with audible beeper to indicate alarm condition Key...

Page 7: ...5 Typical Configuration Permeate Conductivity Probe Shield White Black Cable to Terminal Board Figure 3 Controller Detail CPU 4 Typical Configuration...

Page 8: ...6 Figure 4 Controller Detail Terminal Board TB 1 See Fig 1 for schematic...

Page 9: ...the System On Off switch to turn the system ON 10 Program Mode 2 is default See Table 2 which is a general purpose setting without a flush valve NOTE The Program Settings can be customized to suit the...

Page 10: ...ith the system on Press and Hold the Up and Down Arrows 2 With the Up and Down Arrows depressed Press the System On Off button This will switch to the Hidden Menus as shown above 3 If not already on t...

Page 11: ...op delay Seconds 1 1 1 1 Pump start retry interval restart delay after LP fault Seconds 60 60 60 60 Low pressure fault shutdown of faults Faults 5 5 5 5 Low pressure fault shutdown time period to coun...

Page 12: ...10 Figure 7 Controller Programming Menu Navigation...

Page 13: ...d xxx uS Line 3 Alarm SP xxx ppm or Alarm SP xxx uS Line 4 To Reset Push OFF ON Feed Conductivity Fault Feed conductivity is higher than the alarm set point Line 1 Service Fault Line 2 Feed TDS xxx pp...

Page 14: ...th a multi meter for correct on off operation Replace switch or level control if faulty 3 If someone connected 110v to the terminal strip connection for the high level shut off they could have fried t...

Page 15: ...facturer s warranties on the Product or any parts therein subject to the conditions and exclusions in the manufacturer s warranty Buyer s exclusive remedy under such third party manufacturer s warrant...

Page 16: ...ATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE NO REPRESENTATIONS OR WARRANTIES AT ANY TIME MADE BY ANY EMPLOYEE AGENT OR REPRESENTATIVE OF NELSEN SHALL BE EFFECT...