background image

12

  Controller Fault Condition Displays

If RO Not Working and Display Shows “Tank Full”  or “Tank Full Draw Down”

1.    If using a single point high level float switch, the jumper in the wiring instructions must be installed. This 

needs to be checked to make sure it is not loose and or disconnected, which would cause a failure and 

one of the displays above. ie. Remove jumper and reinstall, making sure of a good connection. Re-check 

display and operation.

2.   Check the switch in the tank to make sure it is operating correctly. Check the switch with a multi-meter for 

correct “on-off” operation. Replace switch or level control if faulty.

3.   If someone connected 110v to the terminal strip connection for the high level shut off, they could have 

fried the “opto-isolator”.  

4.   Also, if there were major lightning strikes and power outages with surges, it is possible that you may have 

had a power surge that sent electric current to the dry contacts and possibly fried the “opto-isolator”.   

This will prevent the system from turning on, and the display will show Tank Full messages.

5.   If the jumper is verified to be in place with good connections, and if the high level cut off switch in the 

storage tank is verified to be operational, then the board might need to be replaced due to number 3 or 4.

Summary of Contents for NRO ROC2HE-UL

Page 1: ...Nelsen NRO ROC2HE UL System Controller Documentation Systems w CPU 4 Control Board Manufactured after March 2020 Since 1954...

Page 2: ......

Page 3: ...Controller Detail TB 1 6 Conductivity Probe Installation Figure 5 7 Installation Instructions 7 Controller Programming Accessing Hidden Menus Figure 6 8 System Start up w Permeate Flush 8 Controller...

Page 4: ...0 6000 s standard sensor CP 1 K 75 Output Circuit Ratings Feed Solenoid 1A Voltage is the same as motor supply voltage Flush Solenoid 1A Voltage is the same as motor supply voltage Motor 1 0 HP 110 12...

Page 5: ...3 Figure 1 Simplified Schematic...

Page 6: ...ard CPU 4 Conductivity Probe Connections Display 4 line 20 character Clear concise feedback on the RO s status Alarm Display backlight flashes along with audible beeper to indicate alarm condition Key...

Page 7: ...5 Typical Configuration Permeate Conductivity Probe Shield White Black Cable to Terminal Board Figure 3 Controller Detail CPU 4 Typical Configuration...

Page 8: ...6 Figure 4 Controller Detail Terminal Board TB 1 See Fig 1 for schematic...

Page 9: ...the System On Off switch to turn the system ON 10 Program Mode 2 is default See Table 2 which is a general purpose setting without a flush valve NOTE The Program Settings can be customized to suit the...

Page 10: ...ith the system on Press and Hold the Up and Down Arrows 2 With the Up and Down Arrows depressed Press the System On Off button This will switch to the Hidden Menus as shown above 3 If not already on t...

Page 11: ...op delay Seconds 1 1 1 1 Pump start retry interval restart delay after LP fault Seconds 60 60 60 60 Low pressure fault shutdown of faults Faults 5 5 5 5 Low pressure fault shutdown time period to coun...

Page 12: ...10 Figure 7 Controller Programming Menu Navigation...

Page 13: ...d xxx uS Line 3 Alarm SP xxx ppm or Alarm SP xxx uS Line 4 To Reset Push OFF ON Feed Conductivity Fault Feed conductivity is higher than the alarm set point Line 1 Service Fault Line 2 Feed TDS xxx pp...

Page 14: ...th a multi meter for correct on off operation Replace switch or level control if faulty 3 If someone connected 110v to the terminal strip connection for the high level shut off they could have fried t...

Page 15: ...facturer s warranties on the Product or any parts therein subject to the conditions and exclusions in the manufacturer s warranty Buyer s exclusive remedy under such third party manufacturer s warrant...

Page 16: ...ATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE NO REPRESENTATIONS OR WARRANTIES AT ANY TIME MADE BY ANY EMPLOYEE AGENT OR REPRESENTATIVE OF NELSEN SHALL BE EFFECT...

Reviews: