background image

11 

Assemble as follows: 

A.  Mark  the  assembly  distance  between  centres  for  the  two  actuators  out  onto  the 

frame in accordance with the measurements in the above table. 

B.  Place the support brackets of the actuator into position, mark 

out  the  holes  for  drilling,  drill  the  frame  and  mount  the 
brackets  (see  “Assembly  for  outward  opening  windows”  for 
details). 

C. Place the front brackets into position, mark out the holes for 

drilling,  drill  the  frame  and  mount  the  front  brackets  (see 
“Assembly for outward opening windows” for details). 

D. Mount  the  actuators  (see  “Assembly  for  outward  opening 

windows” for details) – see Fig.7. 

E.  Mount the connection bar as follows: 

  Insert the connection bar first into one of the actuators, and 

then into the second actuator. Make sure the bar protrudes 
at least 2 mm from each actuator (Fig. 7 bis). 

  Mount  and  screw  the  M8x14  mm  flat  headed  screw 

(provided with connection bar), into the two ends of the bar 
to prevent the bar from slipping out. 

9.  Electrical connections 

The  actuator  comes  with  a  2  m  long  circa  (±5%)  lead  which  has  been  calculated  in 
accordance with safety rules.  
In  the  event  that  the  distance  between  the  actuator  and  the  control  button  should 
exceed this length, the cable should be extended.  
See  table  on  page  8  for conductor  section  indications.  For  harness,  please follow  the 
these diagrams. 

 

Fig. 7 

Fig. 7 bis 

100-240V~ 50/60Hz 

24V

 

100-240V~  

12 

After  connecting  the  electricity  supply  to  the  control  button  (bipolar  with  arrows  if 
possible),  check  that  the  up  key  function  opens  the  window  frame  and  the  and  down 
key  function  closes  it.  In  the  event  of  incorrect  function,  invert  the  two  wires  marked 
light blue and brown in the case of 24V

 motors and invert the two wires marked black 

and brown for 110-230V~ motors. 

 

WARNING:

 after every limit switch or electronic protection device function the 

rack  will  back  track for  around  2  mm  in  the  opposite  direction.  This  is  quite 
normal, and  has  been designed  to  release  tension  on mechanical parts and 
allow complete weather proofing to enhance durability of mechanical parts. 

10. Limit switches 

10.1. 

Stroke-end at opening and closure 

The  limit switch at  opening / closure  is automatic,  electronically  operated  and  cannot  be 
programmed.  The  actuator  stops  when  the  charge  is  absorbed  when  the  window  is 
completely open / closed. 

10.2. 

Stroke adjustment where required 

Factory  settings  for  track  lengths  can  be  shortened  to  regulate  how  much  of  the  rod 
protrudes. This operation must be carried out at the workbench with proper equipment 
by technical personnel qualified to operate with maximum care and safety. 
Procedure: 

1.  Remove the four screws on the front head of the SKY650 actuator. 
2.  Extract the head and rod from the body of the actuator. 
3.  Unscrew the two screws locking the two limit switch block pieces. 
4.  Move the rubber stopper and block to the required position. 
5.  Screw the two screws used for fixing the block into position back in again. 
6.  Re mount everything back onto the body of the actuator. 
7.  Screw  in  the  four  screws  on  the  front  head  and  check  the  settings  for  the  new 

track run. 

11. Checking for correct assembly 

  Check that the frame has closed completely, even at the  corners,  and check there 

are no obstacles caused by assembly in the wrong position. 

  Make sure the actuator is aligned with the axis of the window at 90° to the window 

itself, otherwise the rack will exert incorrect pressure on the rod and consume more 
voltage. 

  Check  the  lead  is  not  too  tight,  as  this  could  damage  the  actuator  during  rotation, 

opening and closing of the window. 

  Check all screws and nuts have been properly tightened. 

 

Summary of Contents for SKY 650

Page 1: ...if repair or adjustment is required CAUTION if the power cable is damaged it must be replaced by qualified personnel from a service centre authorised by the manufacturer CAUTION Disconnect the power...

Page 2: ...ndards and to issue CE certification We strongly discourage any use of the actuators other than that specified and therefore in any case the supplier of the complete system retains full liability For...

Page 3: ...this reason no adjustment is required 4 Construction and standards INTENDED USE The SKY650 rack actuator has been designed and manufactured to open and close top hung windows opening outwards bottom h...

Page 4: ...00 mmq 40 m 600 m 2800 m 1 50 mmq 60 m 900 m 4000 m 2 50 mmq 100 m 1500 m 6800 m 4 00 mmq 160 m 2500 m 11000 m 6 00 mmq 240m 3700 m 15000 m 8 8 Instructions for assembly These indications are intende...

Page 5: ...d out previously and mark the positions for the four holes for the fixing screws Fig 2 C Drill holes into the frame and screw in the motor support bracket making sure that all screws are fitted tightl...

Page 6: ...wires marked black and brown for 110 230V motors WARNING after every limit switch or electronic protection device function the rack will back track for around 2 mm in the opposite direction This is qu...

Page 7: ...ging etc be sent to a centre for ecological recycling as established from laws in force on recycling The device is mainly made from the following materials aluminium zinc iron plastic of various type...

Page 8: ...iva Compatibilit Elettromagnetica ElectroMagnetic Compatibility Directive EMCD 2014 35 EU Direttiva Bassa Tensione Low Voltage Directive LVD 2011 65 EU Direttiva sulla restrizione dell uso di determin...

Reviews: