background image

3

Before installation

Exhaust air operation, 

Fig. 2

Exhaust air is discharged upwards
through a ventilation shaft or directly
through the outside wall into the open.

D

The exhaust air must not be dischar-

ged into a functioning smoke or exhaust
flue or into a shaft used for ventilating
rooms in which stoves are located.

When discharging air into smoke or
exhaust flues which are not in use, local
authority approval is required.

D

When the extractor hood is operated

with exhaust air at the same time as fire
installations that require a chimney
(such as gas, oil or coal-fired central
heating systems, instant water heaters
or hot-water boilers), provision must be
made for an adequate supply of air for
stove combustion.

Safe operation is possible if the under-
pressure in the room where the stove is
installed does not exceed 4 Pa (0.04
mbar).

This can be achieved if the combustion
air can flow through non-closable ope-
nings such as in doors, windows, wall
vent-boxes or other technical features
or arrangements whereby combustion
air can be replenished.

Note: In assessing this possibility, the
entire combined ventilation of the home
must be taken into consideration. This
rule does not apply to operation of coo-
king appliances such as hobs and gas
cookers.

Exhaust air routing must always comply
with local authority regulations.

If the extraction hood is used in recircu-
lating operation - with activated carbon
filter - unrestricted operation is possible.

With exhaust mode, 

a backwash valve

should be installed unless it is already
incorporated in the exhaust pipe or wall
box. (Fig. 3). 
If a backwash valve is not included with
your appliance, your dealer can supply
you with one (see the section on acces-
sories in the operating instructions).

Installation backwash valve:
1.

Cut out the protective grid in the air
connector, Fig. 5.

2.

Insert the backwash valve in the
mounting openings on the air 
connector, Fig. 3.

If the exhaust air is being routed
through the outside wall, 

a telescopic

wall box should be used, Fig. 4.

Connection between extractor hood
and telescopic wall box:

With an exhaust hose or an exhaust
pipe.

Optimal efficiency of the extractor
hood:

Short, smooth exhaust pipe.

As few bends as possible.

Pipe diameter as large as possible
and wide pipe bends.

Round pipes

we recommend a min. inside diame-
ter of 

120 mm.

Flat ducts 

must have an

inside cross-

section equivalent 

to that of the round

pipes.

l

120 mm dia. approx. 113 cm

2

l

150 mm dia. approx. 177 cm

2

In the case of different pipe diame-
ters, 

insert sealing strip.

For exhaust air operation, 

ensure

that there is an adequate supply of
air.

5750.175 652-en  16.11.2006  9:35 Uhr  Seite 3

Summary of Contents for D 26 Series

Page 1: ...Installation instructions for the built in cooker hood D 26 NEFF GB Ltd ...

Page 2: ...fore reading this manual please unfold the illustrations at the back Old appliances still have some resi dual value An environment friendly method of disposal will ensure that valuable raw materials can be recovered and used again Before you dispose of your old applian ce make sure that it has been rendered inoperable Your new appliance was protected by suitable packaging while it was on its way t...

Page 3: ...operation of coo king appliances such as hobs and gas cookers Exhaust air routing must always comply with local authority regulations If the extraction hood is used in recircu lating operation with activated carbon filter unrestricted operation is possible With exhaust mode a backwash valve should be installed unless it is already incorporated in the exhaust pipe or wall box Fig 3 If a backwash va...

Page 4: ...tor comes as standard equip ped with a protective grid in the air connec tor If this is has been removed in the case of exhaust air operation the air connector must be supplemented by a reducer piece with protective grid see section on special accessories in the instruction manual Electrical connection WARNING THIS APPLIANCE MUST BE EARTHED IMPORTANT Fitting a Different Plug The wires in the mains...

Page 5: ...tightened Fig 12 7 Connect pipes 8 Connect electricity Mounting the door Door thickness min 16 mm Door height 380 to 700 mm Door weight max 7 kg In order to match the wall cabinets on either side the door can project at the top and bottom Fig 13 1 Remove the two door carriers to the right and left by pulling both the red plastic catches inwards and removing the door carrier out towards you Fig 14 ...

Page 6: ...40 210 120 230 140 300 140 260 140 290 360 Ventilation capacity in m3 h according to DIN 44971 and freeblowing Technical data Mounting wall covering rail The gap between the hood and the rear wall can be dressed with the enclosed covering rail Fig 18 Screw fasten the covering rail to the underside of the extractor hood Fig 18 Refit the grease filter see instruction manual If the unit door has to b...

Page 7: ...5750 175652 Printed in Germany 1106 Hi NEFF UK Ltd Grand Union House Old Wolverton Road Old Wolverton Milton Keynes MK12 5PT Tel 01908 328300 Fax 01908 328399 ...

Reviews: