PLC messages

The following sections show the different status, warning and alarm messages 

that can be seen in the PLC display.

5.1 

Status messages

The following status messages give information about what mode the unit is in 

or what routine service is being performed.

5.1.1 

L-PAK Off (Off mode)

The unit is in Off mode, which is also the unit’s start menu. The unit can also 

go into Off mode if something is wrong, such as if an alarm is activated. The 

pump motor is off, there is no vacuum, the FCV is closed, and the unit cannot 

be activated by a pilot signal.

5.1.2 

L-PAK Standby (Standby mode)

The unit is in Standby mode and is ready. The pump motor is off, there is no 

vacuum, the FCV is closed, and the unit is waiting for a pilot signal to go into 

Running mode.

Standby

Waiting for

pilot signal

2012-07-02

ESC

OK

5.1.3 

Running (Running mode)

The unit in Running mode. The pump motor is on and the unit generates a 

vacuum. The FCV is closed.

Running

DIRTm 00:00s

OTTmr 00:00s

ESC

OK

DIRTm: The amount of time before the unit goes 

into Idling mode. The default is 10 seconds. See 

also Section 

6.2.4. DIR_Time

.

OTTmr: If the Overtime timer has been 

activated, OTTmr shows the elapsed time since 

the overtime timer started.

5.1.4 

Idling (Idling mode)

The unit in Idling mode. The pump motor is on, there is no vacuum, and the 

FCV is open. The unit goes into Idling mode when there has been no pilot 

signal for the time set in DIR_Time, see Section 

6.2.4. DIR_Time

.

L-PAK

Off

TimeToService

2000Hour

ESC

OK

TimeToService: The amount of time until next 

scheduled service. The default setting is 2000 

hours. See Section 

6.2.3. H-Meter 1

.

Summary of Contents for L-PAK Series

Page 1: ...L PAK Series L PAK 150 250 Advanced 50Hz 60Hz 2130144 00 2016 12 09 Original PLC manual EN PLC MANUAL PLC Manual...

Page 2: ......

Page 3: ...L PAK 150 250 Advanced 3 Figures 4 English 5...

Page 4: ...OK DIR_Time T 10 00s Ta 00 00 FlexPAK Idling TimeToStandby 00 12m ESC OK 4 PS 2 FlexPAK Off Standby TimeToService 2000Hour ESC OK 1 Nederman FlexPAK Off TimeToService 2000Hour ESC OK ESC OK SSR_Time T...

Page 5: ...p 9 5 3 Alarms 9 5 3 1 Alarm Fan Hi Temp 9 5 3 2 Motor Protector Activated 10 5 3 3 Low Pressure CAS 10 6 PLC settings 10 6 1 Find a parameter and set its value 10 6 2 Parameter settings 11 6 2 1 Adju...

Page 6: ...y the carrier and the local Nederman representative immediately 2 Safety This document contains important information that is presented as either a warning caution or note See the following examples W...

Page 7: ...5 SSR_Time The unit stays in Running mode as long as there is an active pilot signal However the unit can still be put into Off mode by pressing the Standby Running button Note that if only one workst...

Page 8: ...ed and the unit is waiting for a pilot signal to go into Running mode Standby Waiting for pilot signal 2012 07 02 ESC OK 5 1 3 Running Running mode The unit in Running mode The pump motor is on and th...

Page 9: ...again in 7 seconds This 1 7 on off sequence continues until the warning is reset Reset the alarm by first putting the unit into Off mode Restart the unit In Standby mode press the manual filter cleani...

Page 10: ...problem and press OK to reset the warning Motor Protector Activated Time when fault occured Reset OK ESC OK 5 3 3 Low Pressure CAS The compressed air level is low When the accurate pressure is establi...

Page 11: ...can be changed 8 Use or to set the value 9 Press OK to confirm 10 Press ESC to go to the main menu 11 Press ESC to go to the date and time screen 12 Press to exit 6 2 Parameter settings The following...

Page 12: ...01 7 The cursor shows the day of the week which flashes since it is the first value that is selected 8 Change the weekday with or 9 Move the cursor to the next position with or 10 Make any other nece...

Page 13: ...the unit is switched off even when a valve remains open for example over night NOTE If the weekly timer has been activated the amount of time the unit can be used during the day before it automaticall...

Page 14: ...nu for setting the service interval The default value is 2000 hours H Meter 1 MI 2000h ESC OK MI 2000h The amount of time between service intervals 6 2 4 DIR_Time Menu for setting the DIR timer The DI...

Page 15: ...ng cycle is 15 seconds 3 TH TL 3 5 15 where TH 02 00s and TL 03 00s ClenCyl TH 02 00s TL 03 00s Ta 00 00 ESC OK TH 02 00s The default time for the FCV to be open TL 03 00s The default time for the FCV...

Page 16: ...is used filter cleaning is not activated until this input is deactivated If this input is activated during a filter cleaning sequence the filter sequence stops immediately and the unit establishes a...

Page 17: ...there is no need to go all the way to L PAK Advanced to restart it 6 9 Standby Ready indicator The H1 lamp Output DO1 acts as a Standby unit ready indicator When the unit is in Standby mode or the fa...

Page 18: ...www nederman com...

Reviews: