FX
2
ESD/EX
4 Installation
WARNING! Risk of personal injury
Always read
before install-
ation, use, service, or troubleshooting of this
product.
4.1 Delivery check
If there are any damaged or missing parts when the
product is delivered, notify the carrier and the local
Nederman representative immediately.
4.2 Mounting instruction
See
The extractor arm can be mounted on a wall, bench,
floor or ceiling. A mounting instruction comes togeth-
er with the accessories wall/ceiling bracket, hood and
bench bracket.
See
. The arm must always be mounted so
that the adjusting knobs on the links are on the right-
hand side.
If a UP-arrow is positioned near the duct connect-
or, the arm must only be installed so that this arrow
points upwards.
NOTE!
The extractor arm must be connected to the
earth according to
. The combina-
tion of extractor arm and extraction system
must be carried out in accordance with require-
ments of explosion prevention and protection
EN 1127-1.
See
. Make sure the arm and the duct are
properly connected.
See
. Do not use a screw with that part of the
arm.
4.2.1 Fitting the gas spring (FX
2
D100 -
L2400 only)
See
(B).
4.3 Earth control measurements after
installation
See
. Earth control measurements must only
be done by a person with appropriate competency of
explosion protected installations.
If a hood (accessory) is used the measuring should be
done from the hood. The ohmmeter must indicate less
than 106 Ω.
NOTE!
• If necessary, use a serrated washer to make
sure there is conductivity.
• Make sure the connected duct system is
grounded according to local regulations.
4.4 Damper, swivel and link adjust-
ments
The links are factory set for normal working positions.
Always check and adjust the links so they will suit the
users preference.
1
Damper open.
2
Damper closed.
5 Use
WARNING! Risk of personal injury
Always read
before install-
ation, use, service, or troubleshooting of this
product.
5.1 Arm position
. Always place the arm as close as pos-
sible to the source. When possible, place the arm side-
ways to the source for best capture, to avoid interfer-
ing with the work process, and to minimize the effect
of the cross draft. See
Always check that the airflow is sufficient in the hood
before work begins. Insufficient airflow can be due to:
• The fan impeller rotates in the wrong direction.
• Hood, arm or ducts are blocked.
For adjustments of damper, swivel and link, see
(A).
6 Maintenance
WARNING! Risk of personal injury
Always read
before install-
ation, use, service, or troubleshooting of this
product.
6.1 Routine inspection and service
Follow the list in
Chapter 10 Appendix B: Maintenance
to routinely inspect, and repair or replace
worn and damaged parts on the inside and outside of
the product.
7 Spare Parts
CAUTION! Risk of equipment damage
Use only N
$
e
$
d
$
e
$
r
$
m
$
a
$
n
$
original spare parts and ac-
cessories.
Contact your nearest authorized distributor or
N
$
e
$
d
$
e
$
r
$
m
$
a
$
n
$
for advice on technical service or
if you require help with spare parts. See also
w
$
w
$
w
$
.
$
n
$
e
$
d
$
e
$
r
$
m
$
a
$
n
$
.
$
c
$
o
$
m
$
.
7.1 Ordering spare parts
When ordering spare parts always state the following:
EN
17
Summary of Contents for FX2 Original Series
Page 8: ...FX2 ESD EX 3 4 8...
Page 9: ...FX2 ESD EX 5 6 7 9...
Page 10: ...FX2 ESD EX 8 9 10...
Page 11: ...FX2 ESD EX 106 106 106 FX Arm ESD 1 x FX Arm EX 2 x EX EX ESD EX ESD EX ESD EX EX 10 11...
Page 12: ...FX2 ESD EX 11 360 360 1 2 A B 12 12...
Page 13: ...FX2 ESD EX A 13 13...
Page 89: ...FX2 ESD EX 9 A 2 ZH 89...
Page 90: ...FX2 ESD EX ZH 10 B 2 OK 90...
Page 91: ...www nederman com...