VP1007-B / Installation manual
Version 01.000 / November 2020 / EN
19
Livestock Management
Error
code
Description
Possible solution(s)
18
Power to next V-pack switched off (max current
and time)
See error code 13 or 19
19
Output voltage to next V-pack too low at activation:
Power to next V-packs switched off.
•
Disconnect all next V-packs
•
Reconnect next V-packs one by one and check
Vi LED (green)
22
Offset voltage on CAN bus too high
•
Check CAN cable for damages or shortcuts
•
Check connectors
23
Output 5: output error. Possibly caused by error 01
to 08.
Check connected device on output 5
Identification performance and disturbance
Identification performance may be decreased by disturbance caused by variable-frequency drives that are used
for ventilation, milk pumps, vacuum pumps, etc. Also ballasts used for fluorescent tube lighting may interfere.
Caution
Most of the time when a variable-frequency drive is causing a problem, it is due to bad installation or the
mandatory main filters have not been installed.
If there is interference, try to locate the source:
1. Follow the instructions in the manual "Optimizing animal identification", which can be obtained from your
dealer or on our Business portal:
http://www.nedap.com/livestockmanagement-portal
.