6�2�4 Install Wizard

The install wizard guides you through the setup of the system parameters.
To prevent accidental system parameter changes, the PowerRouter asks you to login (during commissioning the login is skipped).
The last 4 digits of the serial number on the rating label is used for the login code. Use the Up/Down buttons to set each digit and press the 
YES button to confirm and go to the next digit until the last digit is set.
The following parameters can be set: Language, Country, Date & Time, Battery settings (Size, Current, Type, Charge, Vfloat, Vbulk,  Low 
battery alarm), AC alarm relay.

Install wizard procedure:
1.  Enter the service menu
2.  Select Install wizard
3.  Press YES to enter Install wizard
4.  Press YES to continue the wizard
5.  Enter login code
6.  Press YES to continue the wizard

The table below shows the battery parameters which can be set during the Install wizard or the software installation tool.

Battery settings (right 
relay)

Description

Default 
value

Minimum 
value

Maximum 
value

Size

Capacity of the battery

400 Ah

100 Ah

40000 Ah

Current

Maximum battery charge current

100 A

20 A

200 A

Type

GEL or WET

GEL

Charge*

3 Stage or Fix. float charge characteristic

3 stage

Vfloat

Charge voltage 

26.4 V

26.0 V

28.0 V

Vbulk

Charge voltage if 3-stage charge characteristic is set.
Will not be used if fixed float charge characteristic is set

28.8 V when 
3-stage is set

28.0 V

30.0 V

Low battery alarm

ON: Low battery alarm relay will be activated if battery 
voltage falls below set value

22 V

19.0 V

23.0 V

OFF: Low battery alarm relay will be de-activated if battery 
voltage rises above set value

24 V

24.0 V

26.0 V

* Select float charge for UPS use - select 3 stage for cyclic use.

The table below shows the AC alarm relay parameters which can be set during the Install wizard or the software installation tool.

AC alarm relay (left 
relay)

Description

Default value Minimum 

value

Maximum 
value

AC low alarm

Minimum difference 
between ON and OFF 
setting is 15 V

ON: AC alarm relay will be activated if grid voltage below set 
value

180 V

225 V

OFF: AC alarm relay will be de-activated if grid voltage 
above set value

225 V

230 V

AC high alarm

Minimum difference 
between ON and OFF 
setting is 15 V

ON: AC alarm relay will be activated if grid voltage above set 
value

235 V

254 V

OFF: AC alarm relay will be de-activated if grid voltage 
below set value

230 V

235 V

6�2�5 Internet connection

This clause describes a check if your PowerRouter is connected to the internet.

The internet connection test procedure:
1.  Enter the service menu
2.  Select Internet connection

The display will show information about the internet status like: Internet connection status (ok, error, counting), Last date and time when the 
PowerRouter was internet connected, IP number and status about firmware distribution.

Summary of Contents for PowerRouter

Page 1: ...the PowerRouter PowerRouter Solar Battery Installation Manual...

Page 2: ...tandby 1 2 3 4 x 4 x 2 x 2 x 4 5 6 Standby Standby Standby Standby Standby Standby Standby Standby min 300 mm min 800 mm Max 40 C Min 10 C i 20 KG A A A A A B B Drill template for the PowerRouter Dril...

Page 3: ...C LOCAL OUT AC GRID USB ETHERNET RJ45 CAN BUS CAN NO NO NC NC AC GRID AC LOCAL OUT 2 1 internet router PC laptop Mac to the router Cat5 network cable of a suitable length the PowerRouter to the router...

Page 4: ...Settings menu Service menu Status menu System Reset Selftest Errors Install Wizard Display Date Time Language Battery Solar Grid Battery Solar Grid Internet connections 13 14 YES NO ON OFF Operationa...

Page 5: ...te 20 Manuel d installation Page 34 Installatie handleiding Bladzijde 48 Manuale d installazione Pagina 62 Manual de instalaci n P gina 76 Manual de instala o P gina 90 N V Nederlandsche Apparatenfabr...

Page 6: ...formation that you should know and use to ensure optimal operation of the system A bullet with a number refers to an illustration with the same number For illustrations refer to pages 2 4 Contents To...

Page 7: ...e into account the following guidelines cautions and warnings when choosing a mounting location for the PowerRouter The PowerRouter is designed for indoor installations IP21 Do not install the PowerRo...

Page 8: ...n in a safe and efficient manner follow the steps in the right order Before wiring the PowerRouter make sure that all wires connected to the PowerRouter are not live by turning off all disconnects and...

Page 9: ...PowerRouter Read the label on the battery Battery charging stations must be located in designated battery charging areas This is because of the dangers of hydrogen gas and battery acid Do not smoke or...

Page 10: ...e with the install wizard and installation software tool see also clause 6 2 The left contacts can be used for grid alarms the right contacts can be used for battery alarms 5 Commissioning This chapte...

Page 11: ...or the end user depending on the configuration The restart duration is less than 1 minute Reset procedure 1 Enter the service menu 2 Select Reset 3 Press YES to continue 4 Press YES to start the Reset...

Page 12: ...ill not be used if fixed float charge characteristic is set 28 8 V when 3 stage is set 28 0 V 30 0 V Low battery alarm ON Low battery alarm relay will be activated if battery voltage falls below set v...

Page 13: ...outer to clear the error Also the error message can be cleared using the installation software tool or via the internet Clear error message procedure 1 Press NO for at least 3 seconds Troubleshooting...

Page 14: ...d in Appendix D Solar 8 Disconnect AC wiring Grid Load The PowerRouter can now be removed for disposal or repair Decommissioning should only be carried out by certified persons Contact your installer...

Page 15: ...or inappropriate operation insufficient ventilation of the unit failure to observe the applicable safety regulations force majeure e g lightning overvoltage storm fire cosmetic shortcomings which do...

Page 16: ...isconnects loads B004 S Battery temperature too high measured by the external temperature sensor Check ambient temperature of battery storage room Provide sufficient cooling B005 S Battery temperature...

Page 17: ...upply voltages out of range D029 S Cold start failed D011 S Load voltage too low Check grid voltage D012 S Load voltage too high D013 H Load short circuit Check load D023 H Current overload Disconnect...

Page 18: ...anti islanding regulations electronic fused 6W interactive display with 4 button operation ethernet RJ45 TCP IP 1 second PR50SB BU PR37SB BU PR30SB BU 5 5 kWp and 15 A per string 4 kWp and 15 A per st...

Page 19: ...n the connector locking mechanism PV disconnection procedure 1 Insert PV MS tool with the pins to the connector 2 Pull the PV connector out of the PowerRouter This tool is not delivered with the Power...

Page 20: ...nformationen zu finden die f r einen optimalen Betrieb der Anlage anzuwenden sind Ein nummeriertes Aufz hlungszeichen weist auf eine Abbildung mit derselben Nummer hin Die Abbildungen befinden sich au...

Reviews: