FAULT FINDING CHART
Fault
Igniter does not
spark.
Possible Cause
Spark rod at pilot light shorting.
Faulty spark cable.
Spark cable disconnected.
Corrective Action
Clean Insulator or replace If damaged.
Replace (with genuine part only). Reconnect.
Igniter sparks but
No ignition at pilot
light.
Low batteries.
No Gas.
Replace batteries with new good quality ones.
Check supply. Check AC/DC Power Pack is
plugged in and turned on.
Gas ignites at Pilot
light but goes out
after 5 to 10 seconds.
Air in line.
Pilot light injector blocked.
Low gas pressure
Pilot light air intake blocked (yellow
pilot flame).
Flame sensor cable disconnected.
Purge gas line. Note: reset Igniter by pressing the
on/off switch.
Clear blockage or replace pilot light.
Check incoming gas supply pressure.
Clear Pilot Light air intake hole(s) Inspect cable
and reconnect.
Gas ignites at main
burner but goes out.
Problem with the pilot light.
See above.
Low batteries.
Gas supply line too long and/or
too small.
Gas supply line partly blocked.
Replace batteries with new good quality ones.
Check gas pipe size against AGA code for the
Mjoule rating of appliance.
Clear blockage.
Remote does not
communicate
Low Batteries.
AC/DC Power Pack faulty or not
turned on Unit Switch is “On” or “Off”.
Replace batteries. Check AC/DC Power Pack.
Change to “Remote”.