![background image](http://html1.mh-extra.com/html/nec/express5800-320ma/express5800-320ma_planning-manual_3899134055.webp)
System Specifications
System Specifications
A-5
Table A-1. Pedestal System Specifications
Power
Input power
A-side enclosure: 650W
B-side enclosure: 650W
Nominal input voltage (AC)
100-230 volts +/- 10% 240V + 6%/-10%; 50/60 Hz
Protective earth ground current
3.5 milliamperes maximum for each AC power cord
Physical Dimensions of System in a Pedestal Case
Height
23.25 in. (59.05 cm.)
Width
8.62 in. (21.89 cm); 12.88 in. (32.72 cm)
Depth
31.38 in. (79.71 cm)
Weight, including 8 DIMMS, 4
processors, and 6 disks
Two enclosures: 110 lb (49.9 kg), fully loaded
Case: 68 lb (30.84 kg)
Environmental
Operating temperature
41
°
F to 95
°
F (5
°
C to 35
°
C)
For every 800 ft (243.8m) above 2,000 ft (609.6m),
lower the maximum operating temperature (35
°
C) by
1
°
C.
Storage temperature
-38
°
F to 140
°
F (-40
°
C to 60
°
C)
Operating altitude
0 ft to 10,000 ft (0m to 3,048m)
Maximum rate of temperature
change during operation
18
°
F/hr (10
°
C/hr) or
0.30
°
F/min (0.17
°
C/min)
Relative humidity during
operation
20% to 80% (noncondensing)
Relative humidity during storage
8% to 80%
Heat dissipation
4432 BTUs per hour
Summary of Contents for Express5800/320Ma
Page 1: ...NEC Solutions America Inc NR573 Express5800 320Ma Site Planning Guide...
Page 10: ...Preface x Express5800 320Ma Site Planning Guide...
Page 18: ...System Documentation 1 8 Express5800 320Ma Site Planning Guide...
Page 40: ...Connecting a System Directly to a UPS 5 6 Express5800 320Ma Site Planning Guide...
Page 50: ...Sample PDU Usage Calculation 7 6 Express5800 320Ma Site Planning Guide...
Page 77: ...Standards Compliance Standards Compliance C 3 VCCI Note BSMI Note...
Page 78: ...Standards Compliance C 4 Express5800 320Ma Site Planning Guide...