Determining PDU Requirements
Rack Configuration Planning
7-3
To complete
Table 7-2
1. In column 1, write the names of each system or component in the rack. If you have
more than one system, use a row for each system.
2. In column 2, write the cumulative number of rack units (Us): Add the number of Us
(see
Table 7-1
) for the component to the value in the space above and write the
result.
3. In column 3, write the cumulative number of outlets required. For each component,
add 1 to the value in the space above and write the result.
4. In column 4, write the cumulative current required. For each component, add the
current for the component, which you entered in
Table 7-1
, to the value in the space
above and write the result.
You need another pair of PDUs if the cumulative number of outlets exceeds 8 or if the
cumulative current exceeds 15A. Use the information in column 2 to plan the size and
number of racks required.
Table 7-2. Calculating A-Side PDU and Rack-Space Requirements
1. Component
2. Cumulative
Space Used
3. Cumulative
Number of Outlets
4. Cumulative
Current (A)
PDU Pair
2U
0
0.00
Summary of Contents for Express5800/320Ma
Page 1: ...NEC Solutions America Inc NR573 Express5800 320Ma Site Planning Guide...
Page 10: ...Preface x Express5800 320Ma Site Planning Guide...
Page 18: ...System Documentation 1 8 Express5800 320Ma Site Planning Guide...
Page 40: ...Connecting a System Directly to a UPS 5 6 Express5800 320Ma Site Planning Guide...
Page 50: ...Sample PDU Usage Calculation 7 6 Express5800 320Ma Site Planning Guide...
Page 77: ...Standards Compliance Standards Compliance C 3 VCCI Note BSMI Note...
Page 78: ...Standards Compliance C 4 Express5800 320Ma Site Planning Guide...