Specification
Single Phase MultiCube Page 29
Accuracy
Current
0.2% Ib (1.0% Rdg. 0.05 Ib
≤
I
ph
≤
1.2 Ib) ±1 digit.
Voltage
0.2% Vb (1.0% Rdg. 0.2 Vb
≤
V
ph
≤
1.2 Vb) ±1 digit.
Watts
0.4% FS (1.0% Rdg. 0.05FS
≤
P
≤
1.2FS) ±1 digit.
VA
0.6% FS (1.5% Rdg. 0.05FS
≤
Q
≤
1.2FS) ±1 digit.
var
0.8% FS (2.0% Rdg. 0.05FS
≤
S
≤
1.2FS) ±1 digit.
PF
± 0.2 Degrees
Frequency
±0.05Hz. 45Hz
≤
F
≤
65Hz
Wh
Register
Class 1.0 EN 61036
VAh
Register
Class 2.0
varh
Registers
Class 2.0 IEC 1268
Timebase
Better than 100ppm
Display
Display
Type
Custom, supertwist, LCD with LED backlight
Data
Retention
10 years minimum
Stores energy registers, user settings, and peaks
Display
Format
Display
Update
3 Lines 12mm 3.8mm custom legends
1 second
Digital (Pulse) Outputs
Function
1 pulse / energy unit
(Output #1=N Import Wh, Output #2=N Export Wh)
Scaling
Settable 1,10 or 100 counts of associated register
Pulse
Period
100ms. (2ms Rise, 2ms Fall)
Type
N/O Volt free contact. Optically isolated BiFET
Contacts
100mA AC/DC max, 100V AC/DC max
Isolation
2.5kV (50V #1 to #2)