Specification
Page 28 Single Phase MultiCube
5. Specification
Inputs
System
1-Phase 2 Wire Balanced/Unbalanced Loads
Voltage
Vb. 230 Volt. 1-Phase 2 Wire
Vb. 120 Volt optional
Current
Ib 5 Amp from external current transformer (CT)
Ib 1 Amp optional
Fully Isolated (2.5kV / 1 minute)
Measurement
Range
Voltage
Current
20% to 120%
0.5% to 120%
Frequency
Range
Fundamental
Harmonics
45 to 65Hz
Up to 20th harmonic
Input
Loading
Voltage
Current
Less than 0.1 VA
Less than 0.1 VA
Overloads
Voltage
Current
x2 for 2 seconds maximum
x40 for 0.5 seconds maximum
Auxiliary Supply
Standard
230 Volt 50/60Hz ±15%
Options
110 Volt 50/60Hz ±15%. (Others to order)
Load
5 VA Maximum