Installing the burner into the Comfort boiler:
1.
Install the burner on the side of the boiler
(there should be no shield on the burner, when using the comfort boiler ).
2. Fit the controls either into a cabinet or on the wall.
3. Install the overheating safety cut off into the pocket on the side of the boiler, and connect the
controls so that the overheating safety cut off will cut the power if the boiler overheats.
4. Install the heat sensor on the forward flow, either in the pocket or by the sensor on the for-
ward flow. (The sensor must be insulated to the forward flow.)
5. Fit the pipe on the drop shaft (this must be the pipe that comes with the Comfort boiler).
6. Fit the hopper and auger so that the pipe slopes.
(PELLETS MUST NOT GET STUCK IN THE PIPE.)
Comfort Opop
Height
1050mm 850mm
Width 700mm 380mm
Depth
700mm 560mm
Chimney
130mm 130mm
Forward flow
1 1/4“ 1 1/4“
Back flow
1 1/4“ 1 1/4“
Lining
1/2“ 1/2“
Efficiency
93,3% 89,7%
Dragex
Draught stabilizer
General guidelines:
The boiler should be installed by an authorized fitter and must
be installed in accordance with work supervision publication 42
( Danish ) covering equipment working with water.
The outlet duct should be no longer than 1m,
and should be fitted with a cleaning door.
The chimney draught should be at least 5 PA and should be stable,
a draught stabilizer should always be installed.
If combustion gases condense in the chimney (wet ash)
install a draught stabilizer in the chimney, or open the flue
(the flap inside at the back of the boiler)
as wide as possible to increase the temperature of the smoke.
The boiler must be spanned with a bypass to ensure the back flow is al-
ways kept above 55 degrees.
Manual
NBE pellet system
INSTALLATION GUIDE FOR COMFORT BOILER
Diag. Example of installation