Maximum Liquefied Propane Delivery Capacity
In Thousands of BTU/H (0.5 in WC pressure drop)
Pipe Size
Length (including fittings)
10 ft
(3 m)
20 ft
(6 m)
30 ft
(9 m)
40 ft
(12 m)
50 ft
(15 m)
60 ft
(18 m)
80 ft
(24 m)
100 ft
(30 m)
125 ft
(38 m)
150 ft
(45 m)
175 ft
(53 m)
200 ft
(60 m)
250 ft
(76 m)
1
/
2
in
291
200
160
137
122
110
101
94
89
84
74
67
62
3
/
4
in
608
418
336
287
255
231
212
197
185
175
155
140
129
1 in
1,150
787
632
541
480
434
400
372
349
330
292
265
243
1
1
/
4
in
2,350
1,620
1,300
1,110
985
892
821
763
716
677
600
543
500
1
1
/
2
in
3,520
2,420
1,940
1,660
1,480
1,340
1,230
1,140
1,070
1,010
899
814
749
2 in
6,790
4,660
3,750
3,210
2,840
2,570
2,370
2,200
2,070
1,950
1,730
1,570
1,440