66 NFC Service Manual
Version 1.0
5.1 Error code classification
Classification
Error Code
Error Level
Function
Self-diagnostic / Action
Combustion System
E001
3
2
Overheating of heat exchanger
Manual RESET
Auto RESET
E003
3
Ignition failure
Manual RESET
E004
2
False flame detection
Auto RESET
E012
3
Flame loss
Manual RESET
E016
3
Overheating of heat exchanger
Manual RESET
E030
3
1
Exhaust Overheat: exhaust limit switch shuts
down the unit when the flue temperature
exceeds 230°F(110°C) for more than 10
seconds.
Manual RESET
Alarm
E031
3
Overheating of burner
Manual RESET
E046
2
Abnormal heat exchanger thermistor
Auto RESET
E047
3
2
Abnormal exhaust thermistor
Manual RESET
Auto RESET
E060
1
Abnormal Dual Venturi Limit Switch
Auto RESET
E407
-
Abnormal Hot water outlet 1 sensor
(After mixing valve)
-
E421
-
Abnormal Cold water intake sensor
-
E434
-
Abnormal operation: Water adjust valve
-
E439
-
Abnormal operation: flow sensor
-
E441
-
Hot water outlet 2 (before mixing valve)
-
E445
-
Abnormal operation: Bypass mixing valve
-
E480
-
Abnormal operation: water tank thermistor
Contact technical
support at 1-800-519-
8794.
Air supply System
E109
3
Abnormal FAN motor activity
Manual RESET
E110
3
Exhaust blockage
Manual RESET
-
-
Abnormal APS (open, short, initial value or no
answer)
No error display
CH System
E205
2
Abnormal H / E outlet : thermistor open or
short
Auto RESET
E218
1
Abnormal H / E inlet : thermistor open or short
Alarm
E278
1
Abnormal system supply thermistor
Alarm
E279
1
Abnormal system return thermistor
Alarm
E291
3
Supply / Return inversion limit
Manual RESET
Water supply System
E302
3
Abnormal water pressure (Low pressure)
Manual RESET
E351
-
Abnormal Auto feeder valve
Manual RESET
E352
2
Abnormal water pressure (High pressure)
Auto Reset
E353
2
Abnormal water pressure sensor
Auto Reset
5. Troubleshooting