14        About the Boiler

Air In

Air In

Exhaust 

Gas

Blow Fan

Ignitor

Gas 

Valve

Gas 

Inlet

Flow 

Out

CH 

Return

Three 

-way 

Valve

DHW Heat 

Exchanger

Circulation 

Pump

Heat 

Exchanger

2.6.2    Operating According to Outdoor 

Temperature Conditions

The Outdoor Reset Control feature may be used to enhance 

energy efficiency while maintaining optimal heating 

performance. With the Outdoor Reset Control, the central 

heating temperature setting automatically changes according to 

the outdoor temperature and the K-Factor setting.

You can configure the Outdoor Reset Control settings on the 

front panel in the Central Htg Operation menu. Refer to “10.6.2 

Setting the Central Heating Operation on page 42.

Note

The Outdoor Reset Control feature requires 

installation of an outdoor temperature sensor, and it 

only works when the boiler is running in the normal 

operation mode. It does not work when the boiler’s 

front panel displays a fault.

2.6    Operating Modes

2.6.1    Operating in Central Heating Mode

To operate the central heating mode: 

1.  Press the Menu button (

) to access the Main menu and 

select “2. Central Htg Operation” by pressing the OK button 

(

).

2.  In the Central Htg Operation menu, select “1. Central Htg 

ON/OFF” and select “Enable”. Then, select “1-1 CH Set Temp” 

and select a heating temperature setpoint higher than 

current heating temperature. 

 

When the boiler detects a request for heating production 

(from the installation’s room thermostat, for example), the 

3-way valve goes to heating position and the circulating 

pump starts up.

 

If the boiler water temperature is lower than the desired 

temperature setpoint, the boiler ignites and heats up the 

heating installation until the selected boiler temperature 

is reached. The boiler’s electronic control modulates 

the burner output to adapt to the installation’s heat 

requirements at all times and so that the installation’s 

water temperature remains constant. This prevents the 

installation from overheating and reduces heat loss as 

much as possible.

 

When there is no further heating demand (e.g. when 

the desired ambient temperature selected on the room 

thermostat is reached), the burner is extinguished (if it was 

ignited) and the circulation pump continues to run during 

the post-circulation time (minimum 3 minutes), to protect 

the boiler from overheating due to thermal inertia in the 

installation.

Summary of Contents for NCB500-1.5S/37K

Page 1: ...warranty service always contact an official Technical Assistance Service TAS first Contact the technician or professional who installed your boiler Contact a Gas Safe Registered engineer When contact...

Page 2: ...or explosion may result causing property damage or personal injury Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance WHATTO DO IFYOU SME...

Page 3: ...Setting the DIP Switches 31 7 1 PCB DIP Switches 31 7 2 Front Panel DIP Switches 31 8 Connecting Electrical Supplies 32 8 1 Accessing the Terminal Strips 32 8 2 Connecting the Power Supply Cables 33 8...

Page 4: ...bour s phone call your gas provider and follow their instructions If you cannot reach your gas provider call the fire department Do not return to your home until authorised by your gas supplier or the...

Page 5: ...explosion Do not place combustibles such as newspapers or laundry near the boiler or flue system Doing so may result in a fire Do not place or use hair sprays spray paints or any other compressed gas...

Page 6: ...C Very low scald risk CAUTION Do not turn on the boiler unless the water and gas supplies are fully opened Doing so may damage the boiler Do not turn on the water if the cold water supply shut off va...

Page 7: ...s If LPG conversion is required use the conversion kit supplied with the boiler and attach the item matching the LPG GC No included in the kit The Codes of good practice and regulations refer to the l...

Page 8: ...be dangerous When you no longer wish to use the boiler disable any parts that could be potentially hazardous A B C D E F G 2015 811 2013 dB kW A A A B C D E F G A A KD Navien NCB 24LDWE XL 20 40 Insta...

Page 9: ...aneous hot water production Heat output adjustment Adjustable over entire Max Min output range Type of heating installation Close circuit Max heating operation pressure bar 2 5 Max heating temperature...

Page 10: ...tal coaxial length 80 125 m 27 Max vertical coaxial length 80 125 m 28 Equivalent elbow length 90 80 125 m 2 2 Equivalent elbow length 45 80 125 m 1 0 Equivalent length of adapter 60 100 80 125 m 0 5...

Page 11: ...oad elmax kW 0 034 0 034 At part load elmin kW 0 016 0 016 In standby mode PSB kW 0 003 0 003 Other items Standby heat loss Pstby kW 0 078 0 078 Ignition burner power consumption Pign kW 0 0 Annual en...

Page 12: ...g diagram shows the key components of the boiler Component assembly diagrams and particular parts lists are included in the Appendices NCB700 54C Fan Motor Front Panel Ignitor Flame Rod Circulation Pu...

Page 13: ...Mixing Chamber Primary Heat Exchanger Secondary Heat Exchanger Return Adapter Filter Assembly Gas Valve Central Heating Return Pressure Relief Valve Central Heating Supply DHW Inlet DHW Outlet 3 Way V...

Page 14: ...ter A Flue exhaust Air intake 60 100 80 125 B Central heating supply 22 mm C Hot water outlet DHW 15 mm D Gas supply inlet 22 mm E Cold water inlet DHW 15 mm F Central heating return 22 mm OverheadVie...

Page 15: ...enu and select 2 Central Htg Operation by pressing the OK button 2 In the Central Htg Operation menu select 1 Central Htg ON OFF and select Enable Then select 1 1 CH Set Temp and select a heating temp...

Page 16: ...ture range by k factor setting value and the applicable outdoor temperature range 20 15 10 5 0 10 15 20 25 5 20 30 40 50 60 50 70 80 90 4 3 5 3 2 5 2 1 5 1 2 0 6 1 0 2 Outdoor Temperature C Outdoor Te...

Page 17: ...the NCB500 boiler in its final location A detailed description is given of the procedure in the sequenced sections below Wall mounting Gas connection Electrical connections Flue gases exhaustion syste...

Page 18: ...ainage The boiler produces a significant amount of condensate during operation This condensate must be removed from the boiler and suitably treated if national legislation so requires The boiler shoul...

Page 19: ...boiler in areas where petrol or other flammables are used or stored Ensure that combustible materials are stored away from the boiler and that hanging laundry or similar items do not obstruct access...

Page 20: ...the tongues on the mounting bracket and hang the boiler on the bracket When mounted with the mounting bracket the boiler will have a 16 mm clearance from the back of the wall WARNING The boiler is he...

Page 21: ...d cause leaks Any dirt in the tubes could reduce boiler efficiency and cause it to malfunction Any pipes exposed to the elements or which could freeze in winter must be insulated with suitable insulat...

Page 22: ...3 5 Follow all local codes and regulations when disposing of condensate from the boiler We recommend draining the condensate into a laundry tub as the alkali in laundry detergent will neutralise the...

Page 23: ...terial for the drain line such as PVC or CPVC Do not reduce the size of the drain line to less than 21 5 mm The drain line can be connected to the condensate trap using a condensate trap hose The hose...

Page 24: ...normally after performing an air purge 4 7 Testing the Water System WARNING Ensure that the boiler is full of water before firing the burner Operating the unit without filling it will damage the boil...

Page 25: ...owing recommendations must be complied with at the least Before installing the gas pipes check the type of gas is compatible with the boiler Check that the gas meter in the home can measure the rate o...

Page 26: ...lace away from direct sunlight It must also be thoroughly secured to prevent it from tipping over which could cause an explosion If the boiler is used with propane a gas regulator suitable for this ty...

Page 27: ...t gas pressure reading on the manometer The gas pressure must fall within the ranges specified on page 8 3 Leave the faucet on until the boiler shuts down due to a lack of gas supply and then turn off...

Page 28: ...connecting the flue outlet must be correctly joined using sealing gaskets Ensure that there are no leaks from any part of the removal circuit Switch off the boiler and wait for the pipes to cool down...

Page 29: ...s extended to clear any overhangs 6 2 Flue Installation WARNING The gas removal ducts must not be in contact with or near flammable materials and they must not pass through any structures or walls of...

Page 30: ...8 45 1 0 90 1 5 80 125 27 45 1 0 90 2 2 6 2 2 Vertical Coaxial Removal Type C33 Standard Removal System 80 125 Max length A 28 m 60 100 Max length A 8 m A A Extended Removal System 80 125 Max length A...

Page 31: ...ns of your installation To choose the removal accessories required for each installation see the list of accessories on the NAVIEN price list MaximumTotal Length Type Pipe Diameter mm Orientation Maxi...

Page 32: ...s boiler type capacity burner type country and discharge of condensate function 1 2 3 4 5 6 7 8 ON DIP SW1 Switch Function Setting 1 Boiler Type SOLO ON COMBI OFF 2 Reserve 3 4 Capacity 28kW 3 OFF 4 O...

Page 33: ...t the time of installation Note The NCB500 boiler has an electrical protection degree of IPX5D The electrical connection must be made via a bipolar switch located on the same premises as the boiler Th...

Page 34: ...ether with the seal B 4 Insert all these elements in the cable gland and press on the lid A until the cable is sufficiently fixed in place and the unit is sealed Note The boiler must be connected to t...

Page 35: ...ce This enables our modulating range of OpenTherm room controls to be connected without any further modifications NCB500 OpenTherm Protocol Room Controller 1 2 3 4 5 6 8 3 Connecting the Switched Live...

Page 36: ...a mobile device As the Navien NCB500 boiler has a dedicated connector for the Navien Smart Room Controller on the back of the front panel terminal connection at the terminal block is not required Sim...

Page 37: ...ngeover check the gas inlet pressure Check that the gas circuit is hermetically sealed Check that the control panel is working correctly Check that it functions normally when the boiler is switched on...

Page 38: ...r s schedule programming operation is set f DHW preheat Displayed when the DHW preheat feature is enabled DHW preheat DHW Intelligent DHW preheat Always on DHW preheat Weekly DHW preheat off Eco mode...

Page 39: ...al heating and DHW supply temperatures Refer to the following table for detailed information a b c d e f a Menu button Access to the Main menu screen b Back button Access to the previous screen c OK b...

Page 40: ...mperature will appear on the front panel display after the power is turned on 10 3 Start Up Wizard The setup wizard should run the first time the unit is powered on The wizard must be completed before...

Page 41: ...r temperature 1 Make sure that all hot water taps are closed and ensure that the internal circulator and any external circulating pumps are off 2 In normal operation mode press the Up button The DHW t...

Page 42: ...o the fan target speed Fan Target RPM is only for your reference 10 6 Accessing Basic Menu Items In the Main Menu screen you can view the boiler s operating conditions configure the central heating an...

Page 43: ...input from the outdoor temperature sensor OTC Outdoor Temperature Compensation control will be enabled automatically Also if there is no input from the outdoor temperature sensor OTC control will be d...

Page 44: ...gramming operation press the Menu button and then select 4 Schedule Programming 10 6 3 Setting the DHW Operation To set the boiler s DHW operation press the Menu button and then select 3 DHW Operation...

Page 45: ...ch between the list items or to increase decrease setting values Press the OK button to select an item or to confirm after making changes Press the Back button to return to the previous screen or menu...

Page 46: ...System Information To view the miscellaneous system information press the Menu button and then select 6 EMS Data Press the Up button or the Down button to switch between the information items Press t...

Page 47: ...u Items 10 7 1 Viewing Service Information To view the service information about the boiler press the Back button and the Menu button simultaneously for 3 seconds and then select 1 Service Status Info...

Page 48: ...20 min Default 3 min 8 Freeze protection Set the pump freeze protection temperature Setting range 6 C 10 C Default 10 C Note The system freeze protection temperature is set based on the pump freeze p...

Page 49: ...lt Boiler s minimum heat capacity 11 CH Max Limit Set the central heating maximum heat capacity limit Setting range Central heating minimum capacity limit 20 100 Default 100 12 DHW Min Limit Set the D...

Page 50: ...when detecting the feedback 10 7 4 Diagnosing the Boiler System To run a series of test procedures for a system diagnosis press the Back button and the Menu button simultaneously for 3 seconds and th...

Page 51: ...he operation modes Press the OK button to select an operation mode The boiler resumes operation in normal operation mode if no input is detected for 3 hours Press the Back button to return to the prev...

Page 52: ...HW Outlet thermistor Open or Short Circuit Alarm E421 DHW Inlet thermistor Open or Short Circuit Auto E434 Abnormal operation Flow control value Alarm E441 DHW Outlet 2 thermistor open or short circui...

Page 53: ...l need to drain either both the central heating side and domestic hot water DHW side or one side only before performing maintenance tasks such as cleaning the adapter filter or to prevent the boiler f...

Page 54: ...s still connected Do not close the gas valve except for routine maintenance as this will limit additional freeze protection If the boiler will not be used for an extended period drain the boiler If th...

Page 55: ...beginning of every heating season and or when there is a problem 11 5 Maintenance Schedules Owner maintenance Daily Check boiler area Check pressure temperature gauge Monthly Check flue piping Check...

Page 56: ...may also cause severe property damage 1 Inspect all water and gas piping and verify to be leak free 2 Look for signs of leaking lines and correct any problems found Checking the Flue System and Air P...

Page 57: ...Remind the owner to follow the proper shutdown procedure and to schedule an annual start up at the beginning of the next heating season WARNING Failure to inspect for the above conditions and have th...

Page 58: ...n and is responsible for the connection utilization repair or servicing of gas utilization equipment or accessories who is experienced in such work familiar with all precautions required and has compl...

Page 59: ...bove the gas valve where it is attached to the fan motor assembly Carefully remove the two screws by hand using a Phillips screwdriver and pull the gas inlet pipe away from the fan assembly to access...

Page 60: ...led The Outer packing must be in good condition and must be installed Failure to comply will cause a gas leak resulting in severe personal injury Replace the old Orifice piece with the new part for us...

Page 61: ...up Wizard for gas type selection refer to 10 3 Start Up Wizard on page 39 Measure the CO2 value at low fire If the CO2 value is not within 0 5 of the value listed in Table 2 the gas valve set screw wi...

Page 62: ...e boiler you should clean the heat exchanger annually To clean the heat exchanger 1 Press the Power button on the front panel to turn off the boiler 2 Disconnect the power supply to the boiler 3 Turn...

Page 63: ...sen the three screws holding the front panel and remove the front panel Note When removing the front panel label all wires and make sure all wires are disconnected 7 Use a Phillips screwdriver to remo...

Page 64: ...important to keep electric parts of the boiler safe from water Navien recommends to use a hose If the water pressure of the hose is too high water may splash to other electric parts of the boiler Kee...

Page 65: ...Dip s w 8pin Dip s w 4pin EXT Contact M 7 6 5 4 3 2 1 8 MIX V V CN10 OUTLET_Temp 5 4 3 6 2 CN12 HTL INLET_Temp 2 3 4 CN8 1 CN2 M 7 6 5 4 3 2 1 8 WAV V V CN11 P E 1 2 3 4 1 6 7 8 5 1 0 1 1 1 2 9 1 4 1...

Page 66: ...nt Valve Flow Control DC15V Vent Separation Detector Supply Thermistor Outlet Thermistor 1 Return Thermistor UART Communication Interface FRONT PANEL Communication Interface FUSE Inlet Thermistor 1 EM...

Page 67: ...ensor is on a North or Northeast side of a structure under eaves where the sensor is shielded from direct sunlight Avoid placing sensor in close proximity of heat sources that may affect correct tempe...

Page 68: ...terlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Page 69: ...gister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate C...

Page 70: ...Memo...

Page 71: ...Memo...

Page 72: ...Memo...

Reviews: