background image

18        Maintaining the Boiler

Cleaning the Condensate Trap

1.  Inspect the condensate drain line, condensate fittings, and 

condensate trap.

2.  Remove any sediment in the trap.

3.  Fill with fresh water until the water begins to pour out of the 

drain.

Checking all Piping for Leaks

Eliminate all system or boiler leaks. Continual fresh makeup water 

will reduce boiler life. Minerals can build up in sections, reducing 

heat transfer, overheating heat exchanger, and causing heat 

exchanger failure. Leaking water may also cause severe property 

damage.

1.  Inspect all water and gas piping and verify to be leak free.

2.  Look for signs of leaking lines and correct any problems found.

Checking the Flue Vent System and Air Piping

1.  Visually inspect the entire flue gas venting system and air 

piping for blockage, deterioration or leakage. Repair any 

joints that show signs of leakage. Verify that air inlet pipe is 

connected and properly sealed (if installed).

2.  Verify that boiler vent discharge and air intake are clean and 

free of obstructions.

WARNING

Failure to inspect for the above conditions and have them 

repaired can result in severe personal injury or death.

Checking the Water System

1.  Verify all system components are correctly installed and 

operational.

2.  Check the cold fill pressure for the system. Verify it is correct 

(must be a minimum of 12 psi).

3.  Watch the system pressure as the boiler heats up (during 

testing) to ensure pressure does not rise too high.

Note

 

If the system contains glycol, test for proper 

concentration as recommended by manufacturer.

 

Excessive pressure rise indicates expansion tank 

sizing or performance problem.

4.  Inspect automatic air vents and air separators. Remove air vent 

caps and briefly press push valve to flush vent.

5.  Replace caps. Make sure vents do not leak. Replace any leaking 

vents.

Checking Expansion Tank

 

Expansion tanks provide space for water to move in and out as 

the heating system water expands due to temperature increase 

or contracts as the water cools.

 

Perform annual checks as recommended by manufacturer to 

ensure proper operation.

Checking the Pressure Relief Valves

1.  Inspect the relief valve and lift the lever to verify flow. Before 

operating any relief valve, ensure that it is piped with its 

discharge in a safe area to avoid severe scald potential.

Note

Safety relief valves should be re-inspected 

at least 

once every three years

, by a licensed plumbing 

contractor or authorized inspection agency, to ensure 

that the product has not been affected by corrosive 

water conditions and to ensure that the valve and 

discharge line have not been altered or tampered 

with illegally.

WARNING

Certain naturally occurring conditions may corrode the valve 

or its components over time, rendering the valve inoperative. 

Such conditions are not detectable unless the valve and its 

components are physically removed and inspected. This 

inspection must only be conducted by a plumbing contractor 

or authorized inspection agency – not by the owner. Failure 

to re-inspect the boiler relief valve as directed could result in 

unsafe pressure buildup, which can result in severe personal 

injury, death, or substantial property damage.

Summary of Contents for NCB-180

Page 1: ...navienamerica com For warranty service always contact Technical Support first Contact the technician or professional who installed your boiler Contact a licensed professional for the affected system f...

Page 2: ...fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHATTO D...

Page 3: ...9 3 3 Viewing Basic Information 10 3 4 Resetting the Boiler 11 4 Maintaining the Boiler 12 4 1 Cleaning the Boiler 12 4 2 Draining the Boiler 12 4 3 Cleaning the Inlet Water Filter DHW side 13 4 4 Cle...

Page 4: ...tment C Use only your hand to push in or turn the gas control knob Neverusetools Iftheknobwillnotpushinorturnbyhand don t try to repair it call a qualified service technician Force or attempted repair...

Page 5: ...130 F 55 C 10 seconds 120 F 49 C 10 minutes 100 F 37 C very low scald risk DANGER HOT BURN To prevent burns Use the lowest operating temperature setting necessary to provide comfortably hot water If...

Page 6: ...ler in any other country will void the manufacturer s warranty Should overheating occur or the gas supply fail to shut off turn off the manual gas valve to the appliance WARNING Shut off the gas suppl...

Page 7: ...side the boiler automatically detects the temperature and if necessary initiate a safety heating cycle to prevent internal equipment damage due to freezing temperatures Short Circuit Protection Any sh...

Page 8: ...important information required for the boiler s operation Refer to the following table for detailed information a Space heating mode f S Supply water control Indicates space heating mode operation In...

Page 9: ...t the values required for the boiler s operation such as space heating and DHW supply temperatures Refer to the following table for detailed information k Diagnostics button n Up button For installers...

Page 10: ...er settings menu The boiler will retain your settings during a power outage 3 1 Turning the Boiler On or Off To turn the boiler on or off press the Power button for 0 3 seconds MODE When the power is...

Page 11: ...he water temperature read To prevent burns on page 4 carefully Water above 120 F can cause instant scalding severe burns or death To adjust the water temperature 1 Make sure that all hot water faucets...

Page 12: ...to the Troubleshooting section of this manual or contact Technical Support at 1 800 519 8794 Display Description psi O R S R Outdoor reset curve Not in use 1 Finned tube baseboard 2 FAN coil 3 Cast ir...

Page 13: ...Boiler You will need to drain either both the space heating side and domestic hot water DHW side or one side only before performing maintenance tasks such as cleaning the inlet water filter or to pre...

Page 14: ...require draining and open a purge valve to drain the space heating side Open all domestic hot water faucets completely to drain the water heating side The water that remains in the plumbing lines will...

Page 15: ...rinse it with clean running water cold 4 Reinsert and tighten the strainer 5 Fill the boiler and check for proper operation 4 5 Cleaning the Air Intake Filter If the air intake filter becomes clogged...

Page 16: ...rew 10 Replace the front cover 11 Reconnect the power supply to the boiler 12 Press the Power button on the front panel to turn on the boiler 4 Remove the screw that secures the air intake filter the...

Page 17: ...t there is sufficient make up air to avoid such a situation and the owner is responsible for ensuring that protection against freezing is maintained To avoid freezing issues we strongly recommend the...

Page 18: ...e boiler Failure to perform the service and maintenance could result in damage to the boiler or system Failure to follow the directions in this manual and component literature could result in severe p...

Page 19: ...glycol test for proper concentration as recommended by manufacturer Excessive pressure rise indicates expansion tank sizing or performance problem 4 Inspect automatic air vents and air separators Remo...

Page 20: ...ignition flame detector electrode making sure gasket is in good condition and correctly positioned Checking the Ignition Ground Wiring 1 Check that the ground wire is in good condition and securely a...

Page 21: ...on the supply and return water lines 4 Connect one tube to the A valve and place the free end in the bucket 5 Connect one of the tubes to the circulation pump outlet and the return water line at the B...

Page 22: ...fer to 3 2 Adjusting the Temperature on page 9 Check for cross plumbing between the cold and hot water lines The water from the hot water faucet is too hot Is the set temperature set too high Check th...

Page 23: ...r open or short circuit Contact Technical Support at 1 800 519 8794 E351 Abnormal Auto feeder valve make up water Contact Technical Support at 1 800 519 8794 E352 High water pressure Contact Technical...

Page 24: ...al and shall be subject to Navien s schedule of approved labor allowances Warranty Exclusions Navien s Limited Warranty shall be void in the event of an occurrence of any of the following Improper ins...

Page 25: ...nited States and Canada Removal or alteration of the rating plate OtherTerms This Limited Warranty is subject further to the terms and conditions set forth herein and as may be further specified in th...

Page 26: ...Memo...

Reviews: