Configuration and Installation Chapter 2
SCXI-1160 User Manual 2-8 © National Instruments Corporation
5. If this module is to be connected to an MIO-16 or a DIO-24 data acquisition board, attach the
connector at the metal end of the SCXI-1340 cable assembly to the rear signal connector on
the SCXI-1160 module. Screw the rear panel to the rear threaded strip. Attach the loose end
of the cable to the data acquisition board.
Note: For installation procedures with other SCXI accessories and data acquisition boards,
consult Appendix E, SCXI-1160 Cabling.
6. Check the installation.
7. Turn on the SCXI chassis.
8. Turn on the computer or reconnect it to your chassis.
The SCXI-1160 board is installed and ready for operation.
Signal Connections
This section describes the signal connections to the SCXI-1160 board via the SCXI-1160 front
connector and rear signal connector, and includes specifications and connection instructions for
the SCXI-1160 connector signals.
Note: In high-current applications, the thin layer of gold plating on the relay contact may be
destroyed. Although this will not affect the high current application, you may experience
a high contact resistance in a low-current application and be unable to use the relay.
Caution
!
Connections to and between any terminals of the SCXI-1160 that exceed any of
the maximum ratings of input signals on the SCXI-1160 can result in damage to
the SCXI-1160 module and to the SCXIbus. Maximum input ratings for each
signal are given in this chapter under the discussion of that signal. National
Instruments is not liable for any damages resulting from such signal
connections.