background image

4

|

ni.com

|

RMX-10050/10051 User Guide

Installation

Mounting

This product is designed for mounting in an EIA-310 compliant 19 in. rack. It includes 
adjustable rack ears for mounting in either a flush or recessed configuration. The user is 
responsible for ensuring the mounting method provides adequate structural support for the 
product and any attached cables. Ensure the product is securely mounted before applying power.

Ventilation

The user is responsible for ensuring the mounting location provides adequate ventilation to 
dissipate heat generated during operation of the product. Some models include an air intake on 
the front panel and an exhaust fan on the rear panel. Ensure no external equipment or cables 
restrict the airflow through the intake or exhaust ports. 

Chassis Ground

The rear of the chassis includes a redundant chassis ground screw and ground wire. If desired 
for your installation location, connect the chassis ground wire to the rack cabinet using an 
appropriate fastener.

Main CB Off

Ensure the main CB on the front of the product is in the OFF position before connecting mains 
power.

Facility Power Source

The facility power source or upstream equipment feed for this product must include an 
overcurrent protective device with a maximum rating as shown in the following table.

Table 5.  

Required Facility or Equipment Overcurrent Protection

Model (Part Number)

Related

Continuous Current

Required

Mains Protection

RMX-10050 (785341-01, 785342-01)

16 A

20 A

RMX-10051 (785344-01)

16 A

20 A

RMX-10051 (785343-01)

16 A

20 A

Summary of Contents for RMX-10050

Page 1: ...e are two single phase and two three phase PDUs The following tables provide environmental ratings and feature information Table 1 RMX 10050 10051 Environmental Ratings All Models Category Rating Oper...

Page 2: ...A max with DC disabled RMX 10050 785342 01 Single Phase IEC 60320 C20 100 240 V 2P3W 16A 50 60 Hz C13 100 240V 10 A max per receptacle Total AC output 16 A max RMX 10051 785344 01 Three Phase Wye 4P5W...

Page 3: ...plug as well as a redundant chassis ground screw on the rear panel Ensure that the product is properly grounded before applying power Disconnect all power to the product prior to servicing Do no open...

Page 4: ...panel Ensure no external equipment or cables restrict the airflow through the intake or exhaust ports Chassis Ground The rear of the chassis includes a redundant chassis ground screw and ground wire...

Page 5: ...he rear panel The total DC output is always limited to 500 W This is divided evenly as 125 W per each of the four output channels The ratings table in this manual describes the specific outputs and ra...

Page 6: ...ctors use two low voltage signals as follows Shorting the ENABLE pin to the RETURN pin with a dry contact will trigger the Enable signal Opening the DISABLE pin from the RETURN pin will trigger the Di...

Page 7: ...n 44 196 mm 1 74 in Black 27038 All Outside Surfaces Exhaust Air 4 4 X 0 20 DP Holes 2X Both Sides Off Off On On Breaker Breaker Main Breaker Main Breaker GROUP A GROUP A On On Main Power Main Power P...

Page 8: ...d 4 4 X 0 20 DP Holes 3X Both Sides IEC 60309 6H Exhaust Air Main Breaker Main Breaker DC INHIBIT DC INHIBIT J 8 J 8 DC 1 DC 1 DC 2 DC 2 DC 3 DC 3 DC 4 DC 4 J 3 2 J 3 2 J 3 1 J 3 1 J 2 2 J 2 2 J 2 1 J...

Page 9: ...of the European Communities using the manufacturer s declaration of conformity This system affords the user protection for electromagnetic compatibility EMC and product safety You can obtain the DoC f...

Page 10: ...at ni com patents You can find information about end user license agreements EULAs and third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at n...

Reviews: