USER MANUAL

NI REM-11180

Bus Coupler for Remote I/O

This document describes the features of the NI REM-11180 and contains information about
mounting and operating the device.

EtherCAT

In

EtherCAT

Out

Service

Port

Reset

Button

Local

Bus

U

bus

Power

Supply

Microcontroller

U

L

 (24 V)

GND

RJ45

RJ45

Isolation

Contents

REM-11180 Features................................................................................................................ 2

Ports and Connectors........................................................................................................ 3
Reset Button......................................................................................................................4
LEDs................................................................................................................................. 5

Dimensions................................................................................................................................8
Configuring the Rotary Encoding Switch.................................................................................8
Restoring Default Settings........................................................................................................ 9
Reading Error Codes from REM-11180 IOVs..........................................................................9
Diagnostics..............................................................................................................................10

Diagnosis History Object................................................................................................ 10
Diagnostic Registers........................................................................................................11
User Error Codes.............................................................................................................12
Bus Diagnostic Error Codes............................................................................................19

Summary of Contents for REM-11180

Page 1: ...rt Reset Button Local Bus Ubus Power Supply Microcontroller UL 24 V GND RJ45 RJ45 Isolation Contents REM 11180 Features 2 Ports and Connectors 3 Reset Button 4 LEDs 5 Dimensions 8 Configuring the Rota...

Page 2: ...Features The REM 11180 provides the following features Figure 1 Structure of the REM 11180 S 1 S 2 1 4 5 7 6 2 3 1 Bus connector 2 REM 11180 3 Ethernet connectors 4 Module function label 5 Supply vol...

Page 3: ...rnet Ports 2 1 1 Ethernet In 2 Ethernet Out Table 1 RJ 45 Ethernet Port Pinout Fast Ethernet Signal Pin Pinout TXD 1 1 2 3 4 5 6 7 8 TXD 2 RXD 3 Reserved 4 Reserved 5 RXD 6 Reserved 7 Reserved 8 Figur...

Page 4: ...umpered Figure 4 Service Interface 2 1 1 Label 2 Service Interface Note The service interface is a micro USB port used for factory service and configuration You do not need to connect to this port for...

Page 5: ...t present Figure 7 Status LEDs RUN ERR RDY D E Table 4 Status LED Indicators LED LED Color LED Pattern Indication RUN Off Bus coupler in Init state Green Flashing slowly 2 5 Hz Bus coupler in Pre Oper...

Page 6: ...ms off 200 ms on 1000 ms off watchdog timeout Solid Critical internal error RDY Green Solid Device is ready for operation Green Yellow Flashing Communications power undervoltage or surge voltage Over...

Page 7: ...changed Flashing Access in I O check mode Yellow Red Flashing Bus error during active I O check Red Flashing Local bus error on startup Solid General local bus error Communication error Local bus devi...

Page 8: ...ings and 3D models visit ni com dimensions and search for the module number Figure 9 REM 11180 Dimensions 125 9 mm 4 96 in 122 4 mm 4 82 in 74 0 mm 2 97 in 45 0 mm 1 77 in Configuring the Rotary Encod...

Page 9: ...0 2 Press and hold the reset button 3 Power on the REM 11180 4 Release the button when the RDY LED flashes red and green Reading Error Codes from REM 11180 IOVs When you add the REM 11180 to the RT Ta...

Page 10: ...a ring memory in Overwrite mode The last 16 diagnostic messages are always stored Older messages are deleted Bus coupler and I O errors are stored in the object s diagnostic messages Table 7 Diagnosi...

Page 11: ...is enabled 06 F_ACTIVE_BIT Active The configuration is active PDI to the devices is possible output data is disabled substitute value behavior 07 F_READY_BIT Ready The local bus master is ready for o...

Page 12: ...be completed and then try again 090A Value transmitted in Parameter_Count The number of parameters is inconsistent with the service The Parameter_Count parameter does not agree with the number of subs...

Page 13: ...call 938 Reserved Variable_ID An internal Variable_ID was used Check the call 939 Variable_ID not enabled The Variable_ID is not enabled Password protection Check the call 093A Incorrect Variable_ID...

Page 14: ...n frame connected 0010 Param Ready Parameterization of modules completed 0020 Run Process data traffic running 0080 Force Mode Startup tool specifies outputs 0100 Ready Fail Communication abort in Rea...

Page 15: ...alue with a Variable_ID that contains an unknown code Check the call 0A0D A firmware error occurred Restart the device Contact NI if the problem persists 0A18 Invalid Used_Attributes parameter A reser...

Page 16: ...present with a chip version in the local bus that is not supported Replace the device 0A74 Device number Device of a manufacturer that is not supported present in the local bus Replace the device 0A75...

Page 17: ...the device Contact NI if the problem persists 0A90 Device number Device was selected for synchronization however it does not support this Select a device that supports synchronization or change the s...

Page 18: ...device Contact NI if the problem persists 0B01 A hardware or firmware error occurred Restart the device Contact NI if the problem persists 0B02 A hardware or firmware error occurred 0B03 A hardware o...

Page 19: ...r Codes Code hex Additional code Meaning Remedy 0BD1 The bus could not be activated due to bus malfunctions Check the bus configuration 0BF1 0BF2 0BF3 0C01 Device number The configured module is not a...

Page 20: ...instance ID Check the configuration Adapt the configuration frame if the modification was done on purpose 0C13 Device number The process data length does not correspond to the configured value The pr...

Page 21: ...Check the I O supply 3412 Sensor supply not present I O supply voltage failure 3422 Actuator supply not present 5112 Faulty 24 V supply 24 V supply fail Short circuit or overload at the 24 V supply 24...

Page 22: ...der 7610 Receive buffer full Rx Buf full Read the receive buffer 7611 Transmit buffer full Tx Buf full Check the handshake 7620 EPROM device error CS ROM Restart the device Replace the device if the e...

Page 23: ...he service used cannot be applied to this object 0607 Object does not exist 0608 Type conflict 0800 xx30 A reserved bit or reserved code was used during parameterization xx Number of the affected elem...

Page 24: ...ible bus error Check the bus configuration 0F12 Device cannot be reached timeout Check the device 0F13 Device not accessible because it was removed Check the bus configuration 0F21 Invalid device numb...

Page 25: ...be overwritten 20 Service cannot be executed at present 21 Due to local control service cannot be executed at present 22 Service cannot be executed in current device state device control 23 Service ca...

Page 26: ...ication Engineers Visit ni com services for NI Factory Installation Services repairs extended warranty and other services Visit ni com register to register your NI product Product registration facilit...

Page 27: ...niglobal to access the branch office websites which provide up to date contact information support phone numbers email addresses and current events REM 11180 User Manual National Instruments 27...