Code
(hex)
Additional code
Meaning
Remedy
0A7C
—
Invalid Dev_Length specified
during loading.
Check the parameters.
0A81
Object index
Service (e.g,
Create_Configuration) could not
be executed due to PDI
communication malfunctions
(timeout).
Restart the device.
Contact NI if the
problem persists.
0A82
Object index
Service (e.g,
Create_Configuration) could not
be executed due to PDI
communication malfunctions
(number).
Restart the device.
Contact NI if the
problem persists.
0A83
Object index
Service (e.g,
Create_Configuration) could not
be executed due to PDI
communication malfunctions
(error).
Restart the device.
Contact NI if the
problem persists.
0A90
Device number
Device was selected for
synchronization, however it does
not support this.
Select a device that
supports
synchronization or
change the selection.
0A91
Device number
Device was selected for
synchronization, however it does
not support the specified cycle
time.
Select a different cycle
time or a different
device.
0A92
Device number
Device was selected for
synchronization, but does not
support the specified value for
Input_Delay.
Select a different value
for Input_Delay or a
different device.
0A93
Device number
Device was selected for
synchronization, but does not
support the specified value for
Output_Delay.
Select a different value
for Output_Delay or a
different device.
REM-11180 User Manual
|
© National Instruments
|
17